YOKOGAWA Admag TI Series User Manual page 171

Foundation fieldbus communication type
Hide thumbs Also See for Admag TI Series:
Table of Contents

Advertisement

Relative
Index
Parameter Name
Index
10
1010
MANUFAC_ID
11
1011
DEV_TYPE
12
1012
DEV_REV
13
1013
DD_REV
14
1014
GRANT_DENY
15
1015
HARD_TYPES
16
1016
RESTART
17
1017
FEATURES
18
1018
FEATURE_SEL
19
1019
CYCLE_TYPE
20
1020
CYCLE_SEL
21
1021
MIN_CYCLE_T
22
1022
MEMORY_SIZE
23
1023
NV_CYCLE_T
24
1024
FREE_SPACE
25
1025
FREE_TIME
Write
Default Value
Mode
0x594543
-
0x16
-
1
-
1
-
0x00
AUTO
0x00
AUTO
0x0007
-
1
AUTO
0x041E
-
0x000E
AUTO
0x0001
-
0x0000
AUTO
3200
-
0
-
0
-
0.0
-
0.0
-
<6. Parameter Lists>
Description
Manufacturer identification number
(ID No.) used by an interface device
to locate the DD for the resource. The
manufacturer identification number of
Yokogawa is 5850435 (0x594543).
ID number assigned to the device. The
ID number for AXG is 0x0016, and for
AXW 0x0017.
Device revision number.
Revision number in the device
description of the device.
The parameter for checking if various
operations have been executed. Set
a bit corresponding to the GRANT
parameter before various operations are
executed. Check the DENY parameter
after the operation. If the bit for the
operation is not set, it indicates that the
operation was executed. Bit assignment
complies with the Communication
standard specifications.
Bit string indicating the types of
hardware (device).
Bit0: Scalar input analog input
Bit1: Scalar output analog output
Bit2: Discrete input digital input
Bit3: Discrete output digital output
Indicates how the device re-starts up.
1: Run: Running
2: Resource: Re-start
3: Defaults: Re-start with default value on
FF specifications*1
4: Processor: Re-start of CPU
Determines option operations of the
resource block. Bit assignment complies
with the Communication standard
specifications.
Parameter to used to select resource
block options. Options defined
in FEATURES can be selected.
Bit assignment complies with the
Communication standard specifications.
Bit string indicating the type of cycle
which the resource can execute. Bit0:
Scheduled: Used by scheduling
Bit1: Event driven: Used by event-driven
type
Bit2: M anufacturer specified: Can be
used with unique function
Bit string to select the type of cycle.
Minimum value of period of execution.
Memory size available to configure the
function block mounted in this device.
To be checked before attempting a
download.
Sets the interval between writing copies
of nonvolatile parameters to EEPROM.
Percent of remaining memory available
for further configuration. For this
product, 0 is shown, which means a
preconfigured resource.
Percent of the block processing time
that is free to process additional blocks.
Not used for this product.