B.2 Parameter Table
No.
Name
C6-03
Carrier Frequency Upper Limit
C6-04
Carrier Frequency Lower Limit
C6-05
Carrier Frequency Proportional Gain
<1> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 2-OLV control.
<2> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control.
<3> Default setting value is dependent on parameters o2-04, Drive/kVA Selection, A1-02, Control Method Selection and C6-01, Normal/Heavy Duty selection. 351.
<6> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range becomes 0.00 to 600.00 seconds.
<8> Default setting value is dependent on parameter C6-02, Carrier Frequency Selection.
<22> Parameter can be changed during run.
<23> Parameter cannot be changed during run when parameter A1-02 = 5-PM OLV Control.
u
d: References
Reference parameters are used to set the various frequency reference values during operation.
No.
Name
d1-01
<22>
Frequency Reference 1
d1-02
<22>
Frequency Reference 2
d1-03
<22>
Frequency Reference 3
d1-04
<22>
Frequency Reference 4
d1-05
<22>
Frequency Reference 5
d1-06
<22>
Frequency Reference 6
d1-07
<22>
Frequency Reference 7
d1-08
<22>
Frequency Reference 8
d1-09
<22>
Frequency Reference 9
d1-10
<22>
Frequency Reference 10
d1-11
<22>
Frequency Reference 11
d1-13
<22>
Frequency Reference 13
d1-14
<22>
Frequency Reference 14
d1-15
<22>
Frequency Reference 15
d1-16
<22>
Frequency Reference 16
d1-17
<22>
Jog Frequency Reference
d2-01
Frequency Reference Upper Limit
d2-02
Frequency Reference Lower Limit
300
Description
Open Loop Vector: C6-03 defines the fixed carrier frequency if C6-02 = F.
V/f control: C6-03 and C6-04 set upper and lower limits for the carrier
frequency.
carrier frequency
C6-03
C6-04
output frequency
× (C6-05) × K
The coefficient K depends on C6-03:
C6-03 ≥ 10.0 kHz: K = 3
10.0 kHz > C6-03 ≥ 5.0 kHz: K = 2
5.0 kHz > C6-03: K = 1
When C6-05 ≤ 6, C6-04 is disabled (makes the carrier frequency C6-03 value).
Sets the relationship of output frequency to carrier frequency when C6-02 =
F.
Description
d1: Frequency Reference
Use d1 parameters to configure the drive frequency reference.
Frequency reference
Frequency reference when digital input "Multi-Step Speed Reference 1" (H1-oo
= 3) is on.
Frequency reference when digital input "Multi-Step Speed Reference 2" (H1-oo
= 4) is on.
Frequency reference when digital inputs "Multi-Step Speed Reference 1, 2" (H1-
oo = 3 and 4) are on.
Frequency reference when digital input "Multi-Step Speed Reference 3" (H1-oo
= 5) is on.
Frequency reference when digital inputs "Multi-Step Speed Reference 1, 3 " (H1-
oo = 3 and 5) are on.
Frequency reference when digital inputs "Multi-Step Speed Reference 2, 3" (H1-
oo = 4 and 5) are on.
Frequency reference when multi-function input "Multi-Step speed reference 1, 2,
3" (H1-oo = 3, 4, 5) are on.
Frequency reference when multi-function input "Multi-Step Speed Reference
4" (H1-oo = 32) is on.
Frequency reference when digital input "Multi-Step Speed Reference 1, 4" (H1-
oo = 3 and 32) are on.
Frequency reference when digital inputs "Multi-Step Speed Reference 2, 4" (H1-
oo = 4 and 32) are on.
Frequency reference when digital inputs "Multi-Step Speed Reference 3, 4" (H1-
oo = 5 and 32) are on.
Frequency reference when digital inputs "Multi-Step Speed Reference 1, 3, 4" (H1-
oo = 3, 5, 32) are on.
Frequency reference when digital inputs "Multi-Step Speed Reference 2, 3, 4" (H1-
oo = 4, 5, 32) are on.
Frequency reference when digital inputs "Multi-Step Speed Reference 1, 2, 3,
4" (H1-oo = 3, 4, 5, 32) are on.
Frequency reference when digital inputs "Jog Frequency Reference", "Forward Jog"
or "Reverse Jog." are on. "Jog Frequency Reference" has priority over "Multi-Step
Speed Reference 1 to 16".
d2: Frequency Upper and Lower Limits
Use d2 parameters to configure the frequency reference limits.
Sets the frequency reference upper limit as a percentage of maximum output
frequency (E1-04). Output speed is limited to this value even if the frequency
reference is higher. This limit applies to all frequency reference sources.
Sets the frequency reference lower limit as a percentage of maximum output
frequency (E1-04). Output speed is limited to this value even if the frequency
reference is lower. This limit applies to all frequency reference sources.
output
frequency
E1-04
max output
frequency
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Control
Mode
Range
Def.
V/f OL V PM
1.0 to 15.0
A
A
A
<8>
0.4 to 15.0
A
-
-
<8>
00 to 99
A
-
-
<8>
Control
Mode
Range
Def.
OL
V/f
PM
V
0.00 to 400.00
Hz
0.00 Hz
S
S
S
<11>
<19>
0.00 Hz
S
S
S
0.00 Hz
S
S
S
0.00 Hz
S
S
S
0.00 Hz A
A
A
0.00 Hz A
A
A
0.00 Hz A
A
A
0.00 Hz A
A
A
0.00 Hz A
A
A
0.00 Hz A
A
A
0.00 Hz A
A
A
0.00 Hz A
A
A
0.00 Hz A
A
A
0.00 Hz A
A
A
0.00 Hz A
A
A
6.00 Hz
S
S
S
0.0 to 110.0 100.0%
A
A
A
0.0 to 110.0
0.0%
A
A
A
Addr.
Pg.
Hex
225
—
226
—
227
—
Addr.
Pg.
Hex
76
280
281
76
76
282
283
76
284
—
285
—
286
—
287
—
288
—
28B
—
28C
—
28E
—
28F
—
290
—
291
—
292
76
289
—
28A
—