F6 And F7: Serial Communications Option Card Settings - YASKAWA V1000 Series Technical Manual

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

5.6 F: Option Settings
u

F6 and F7: Serial Communications Option Card Settings

F6-01: Communications Error Option Selection
n
Parameter Overview
No.
F6-01
Communications Error Operation Selection
F6-02: External Fault from Comm. Option Selection
n
Parameter Overview
No.
F6-02
External Fault from Comm. Option Selection
F6-03: External Fault from Comm. Option Operation Selection
n
Parameter Overview
No.
F6-03
External Fault from Comm. Option Operation Selection
F6-04: Trace Sampling Rate
n
Parameter Overview
No.
F6-04
Trace Sampling Rate
F6-10: CC-Link Node Address
n
Parameter Overview
No.
F6-10
CC-Link Node Address
F6-11: CC-Link Communication Speed
n
Parameter Overview
No.
F6-11
CC-Link Communication Speed
F6-14: BUS Error Auto Reset
n
Parameter Overview
No.
F6-14
BUS Error Auto Reset
F6-20: DeviceNet MAC Address
n
Parameter Overview
No.
F6-20
DeviceNet MAC Address
F6-21: DeviceNet Communication Speed
n
Parameter Overview
No.
F6-21
DeviceNet Communication Speed
156
Name
Selects the operation after a communications error occurred.
0: Ramp to stop using current accel/decel time
1: Coast to stop
2: Fast Stop using C1-09
3: Alarm only
Name
Sets when an external fault from a comm option is detected.
0: Always detected
1: Detection during Run only
Name
Selects the operation after an external fault set by a communications option
(EF0).
0: Ramp to stop using current accel/decel time
1: Coast to stop
2: Fast Stop using C1-09
3: Alarm only
Name
Name
Name
0: 156 Kbps
1: 625 Kbps
2: 2.5 Mbps
3: 5 Mbps
4: 10 Mbps
Name
Name
Name
0: 125 kbps
1: 250 kbps
2: 500 kbps
3: Detect automatically
Description
Description
Description
Description
-
Description
Sets the node address if a CC-Link option card is installed
Description
Description
Selects if a BUS fault can be automatically reset.
Description
Selects the drives MAC address for DeviceNet
Description
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Range
Default
0 to 3
1
Range
Default
0 or 1
0
Range
Default
0 to 3
1
Range
Default
0.0 to 5.0
2.0 s
Range
Default
0 to 63
0
Range
Default
0 to 4
0
Range
Default
0 or 1
0
Range
Default
0 to 63
0
Range
Default
0 to 3
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents