YASKAWA V1000 Series Technical Manual page 115

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

*This value is C1-02 or the selected deceleration time.
b1-04: Reverse Operation Selection
n
For some applications, reverse motor rotation is not appropriate and may even cause problems (e.g., air handling units, pumps, etc.). Setting parameter
b1-04 to 1 will cause the drive to ignore any inputs for reverse operation. .
No.
Name
b1-04
Reverse Operation Selection
Note: The default setting for b1-04 is 0, which allows reverse operation. To prohibit the drive from operating in reverse, set b1-04 to "1".
b1-07: LOCAL/REMOTE Run Selection
n
When the drive is switched between the LOCAL (operation using the digital operator) to REMOTE (these settings are determined by b1-01 and b1-02),
there is the possibility that a run command is already present (i.e., a switch closure between S1 and SN when b1-02 = 1). Parameter b1-07 determines
what the drive will do if a run command is still present when switching between LOCAL and REMOTE.
No.
Name
b1-07
LOCAL/REMOTE Run Selection
Detailed Description
0: If the run command is closed when switching from LOCAL or alternative reference to REMOTE, the drive will not run.
The drive ignores an external run command until it is removed and re-instated.
1: If the run command is closed when switching from LOCAL or alternative reference to REMOTE, the drive will run.
The drive accepts a run command if it is already present and immediately begins accelerating to the specified frequency reference.
WARNING! The drive may start unexpectedly if switching from LOCAL to REMOTE when b1-17 = 1. Clear all personnel away from rotating machinery and electrical connections
prior to switching between LOCAL and REMOTE. Failure to comply may cause death or serious injury.
b1-08: Run Command Selection while in Programming Mode
n
As a safety precaution, the drive will not normally respond to a run input when the digital operator is being used to adjust parameters. If it is necessary to
recognize external run commands while programming the drive, set b1-08 to "1".
No.
Name
Run Command Selection while in
b1-08
Programming Mode
Note: Refers collectively to the Verify Menu, the Setup Mode, Parameter Settings Mode, and Auto-Tuning.
b1-14: Phase Order Selection
n
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
No.
Name
Sets the phase order for drive output terminals U/T1, V/T2 and W/T3.
b1-14
Phase Order Selection
0: Standard
1: Switch phase order
b1-15: Frequency Reference Selection 2
n
Refer to the detailed description for parameter b1-01.
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Run Wait Time t
Decel Time
*
(C1-02)
Minimum
Baseblock Time
(L2-03)
Minimum Output Frequency
Sets the forward rotation of the motor, and if reverse operation is disabled.
0: Reverse enabled.
1: Reverse disabled.
Determines how the drive will interlock when the source of the run command switches from LOCAL to REMOTE.
Note that one of the H1 parameters be set to 2 in order to use this function.
0: Cycle External RUN - If the run command is closed when switching from LOCAL to REMOTE, the drive will
not run. The run command must first be shut off and then entered again in order to operate the motor.
1: Accept External Run - If the run command is closed when switching from LOCAL to REMOTE, the drive will
run.
0: Disabled - Run command accepted only in the operation menu.
1: Enabled - Run command accepted in all menus.
2. Prohibit entering programming mode during run.
Output Frequency
When Stop Command
is Entered
100%
(Max Output Frequency)
Setting Range
Setting Range
Setting Range
Setting Range
5.2 b: Setup
Default
0
Default
0
Default
0
5
Default
0
115