YASKAWA V1000 Series Technical Manual page 112

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

5.2 b: Setup
b1-02: Run Command Selection 1
n
Parameter b1-02 determines where the run command and stop command are input from.
Note: The run command and the frequency reference can be supplied to the drive using various sources that include the operator, the control circuit terminals, option cards, serial
communications, and Pulse Train input. The settings required by the drive to accept each one of these input sources can vary. Be sure to read the directions carefully and make
the all appropriate settings.
No.
Name
b1-02
Run Command Selection 1
Detailed Description
Available selections for b1-02 include:
Setting
0
Operator: RUN and STOP keys on the LED or LCD operator
1
Terminals: Contact closure on terminals S1 or S2
2
Serial Communications: Modbus RS-422/485 terminals R+, R-, S+ and S-
3
Option PCB
0: Operator
To use the operator to control the drive, press
motor.
1.
Turn on the power to the drive. The initial display appears.
2.
Set the frequency reference to F6.00 (6 Hz).
RUN
3.
Press the
key to start the motor. The RUN indicator LED will light and the motor will begin rotating at
6 Hz..
4.
Press the
key to stop the motor. The RUN light will flash until the motor comes to a complete stop.
1: Control Circuit Terminal
To issue the run command from the terminals, set b1-02 to "1" and select between 2-wire and 3-wire control operation. The default setting is for 2-wire
control.
2-Wire Control
The drive is defaulted for 2-wire operation. In the 2-wire configuration, a closure between S1 and SN is interpreted as a forward run command by the
drive. A closure between S2 and SN is interpreted as a reverse run command. If both S1 and S2 are closed, the drive will stop (decelerate to zero speed)
and the digital operator will display an external fault alarm ("EF" flashes).
Control Circuit Terminal
S1
S2
3-Wire Control
When any of the multi-function digital input parameters (H1-01 through H1-05) are set to 0, terminals S1 and S2 become run and stop, respectively. The
multi-function digital input that was set to 0 will function as a forward/reverse input for the drive. When the forward/reverse input is open the drive will
run in the forward direction and when the input is closed, the drive will run in reverse.
In 3-wire operation, a momentary closure (> 50 ms) of S1 will cause the drive to run provided that S2 is held closed. The drive will stop any time the S2-
SN connection is broken. If the 3-wire configuration is implemented via a 3-wire initialization (A1-03= 3330), then terminal S3 becomes the forward/
reverse input.
112
Selects the run command input source.
0: Operator - RUN and STOP keys on the digital operator.
1: Terminals - Contact closure on terminals S1 or S2.
2: Serial Com - Modbus RS-422/485 terminals R+, R-, S+ and S-.
3: Option PCB.
or set b1-02 to "0". This puts the drive in LOCAL mode. In this setting, use the
Forward Run
Reverse Run
Figure 5.4 2-Wire Control
Description
Description
ON
Forward run
Reverse run
Drive
S1
S2
SC
Digital Input Common
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Default
RUN
and
keys to start and stop the
STOP
off
on
flashing
off
OFF
Stop
Stop
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents