5.8 L: Protection Functions
L8-15: OL2 Characteristics Selection at Low Speeds
n
At very low speeds (6 Hz and below) and very high current levels it can be possible to damage output transistors. Therefore the default setting of L8-15
is set to shorten the time before an OL2 fault will occur when operating at low speed with a relatively heavy load (L8-15 = "1: Enabled").
L8-18: Software CLA Selection
n
The Software CLA (software current limit level) is a drive protection function that will limit the drive's output current. The drive limits the output current
by reducing the output frequency whenever the current exceeds 110% of the drive rated current. If the current level drops below the Software CLA level,
then normal operation will continue.
If the software current limit is disabled (L8-18 = "0: Disabled"), the drive may trip on an OC fault if the load is prohibitively large or the acceleration is
too short. For proper drive protection and operation leave the Software CLA function enabled.
L8-19: Frequency Reduction Rate during OH Pre-Alarm
n
Specifies how much to derate the frequency reference when L8-03 is set to 4 and an OH prealarm is output.
L8-29: Current Unbalance Detection (LF2)
n
This function is available only when using PM Open Loop Vector.
Issues a stop command when the output current becomes unbalanced as a result of a damaged photocoupler or output phase loss. Set to 0 to disable this
function.
L8-35: Side-by-Side Installation Selection
n
Sets the type of installation. Default setting is for a standard type of set up. For a fully enclosed motor compliant with NEMA type 1 specifications, set
this parameter to "2". Set to "1" when taking advantage of Yaskawa's Side-by-Side installation.
L8-38: Carrier Frequency Reduction
n
Specifies the degree of reduction for the carrier frequency at low speeds for IGBT protection. There is no carrier frequency reduction when L8-38 is set
to 0. Set to "1" to derate the carrier frequency when operating at less than 6 Hz and during overload.
To always have a derated carrier frequency, set L8-38 to 2.
L8-40: Low Carrier Frequency Time
n
Sets the amount of time the drive will operate with a reduced carrier frequency. The carrier frequency derating function during run is disabled when this
parameter is set to 0.00 s.
L8-41: Current Alarm Selection
n
Allows or restricts an alarm from being triggered when the relative output current rises above 150%. Disabled when set to 0 (no output).