The drive has a built-in self-diagnosing function of the serial communication interface circuits. To perform the self-diagnosis function use the following
procedure.
1. Turn on the power to the drive.
2. Set terminal S7 for the communications test mode (H1-07 = 67).
3. Turn off the power to the drive.
4. With the power off, wire the drive as shown in the illustration below.
5. The last slave in the series should have DIP switch 2 placed to the ON position in order to enable terminal resistance.
6. Turn the power to the drive back on. The DIP switch setting takes affect after the drive is turned on again.
During normal operation, the drive will display PASS. This indicates that the communications test mode is operating normally. When a fault occurs, the
drive will display CE on the keypad screen. Once the output contact closes, the "Drive Ready" signal will open.