3.7 Control Circuit Wiring
Wire Size and Torque Specifications
n
Select the appropriate wires and crimp terminals from
to Ferrule Terminal Types and Sizes on page
Terminal
Screw Size
MA, MB, MC
M3
S1-S7, SC, RP, +V,
A1, A2, AC, HC, H1,
M2
P1, P2, PC, MP, AM,
AC, S+, S-, R+, R-, IG
Ferrule-Type Wire Terminations
n
Crimp a ferrule to signal wiring to improve wiring simplicity and reliability. Use CRIMPFOX ZA-3, a crimping tool manufactured by PHOENIX
CONTACT.
2
Size mm
(AWG)
0.25 (24)
0.34 (22)
0.5 (20)
0.75 (18)
1.0
u

Wiring Procedure

This section describes the proper procedures and preparations for wiring the terminal board.
WARNING! Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on. Failure to comply could result in death or serious injury.
NOTICE: Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2, W/T3, -, +1, +2) and other high-power lines. Improper wiring
practices could result in drive malfunction due to electrical interference.
NOTICE: Separate wiring for digital output terminals MA, MB and MC from wiring to other control circuit lines. Improper wiring practices could result in drive or equipment malfunction
or nuisance trips.
NOTICE: Use a class 2 power supply (UL standard) when connecting to the control terminals. Improper application of peripheral devices could result in drive performance degradation
due to improper power supply.
NOTICE: Insulate shields with tape or shrink tubing to prevent contact with other signal lines and equipment. Improper wiring practices could result in drive or equipment malfunction
due to short circuit.
NOTICE: Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment grounding could result in drive or equipment malfunction or nuisance trips.
Wire the terminal board using
Figure 3.23
Refer to Wire Gauges and Tightening Torque on page 41
in
.
NOTICE: Do not tighten screws beyond the specified tightening torque. Failure to comply may damage the terminal block.
NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices could result in drive or equipment malfunction due to electrical
interference.
46
Table 3.10
46.
Table 3.9 Wire Size and Torque Specifications (Same for All Models)
Tightening
Tightening Torque
Torque
(in-lbs)
N•m
0.5 to 0.6
4.4 to 5.3
0.22 to 0.25
1.9 to 2.2
Figure 3.21 Ferrule Dimensions
Table 3.10 Ferrule Terminal Types and Sizes
Type
L (mm)
AI 0.25-6YE
10.5
AI 0.34-6TQ
10.5
AI 0.5-6WH
12
A1 0.75-6GY
12
AI 1-6RD
12
Figure 3.22
as a guide (control circuit terminal block). Be sure to prepare the ends of the control circuit wiring as shown
. Crimp a ferrule to signal wiring to improve wiring simplicity and reliability.
Bare Wire Terminal
Applicable wire size
Recomm. mm
mm
2
(AWG)
(AWG)
Stranded: 0.25 to 1.5
(24 to 16)
0.75 (18)
Single: 0.25 to 1.5
(24 to 16)
Stranded: 0.25 to 1.0
(24 to 18)
0.75 (18)
Single: 0.25 to 1.5
(24 to 16)
f d1
f d2
d1 (mm)
d2 (mm)
0.8
2
0.8
2
1.1
2.5
1.3
2.8
1.5
3.0
for tightening torque specifications.
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Ferrule-Type Terminal
Applicable wire size
2
Recomm. mm
mm
2
(AWG)
(AWG)
0.25 to 1.0
0.5 (20)
(24 to 18)
0.25 to 0.5
0.5 (20)
(24 to 20)
Manufacturer
PHOENIX CONTACT
Refer
Wire Type
2
Shielded line,
etc.