5.7 H: Terminal Functions

5.7

H: Terminal Functions

H parameters are used to assign functions to the external terminals.

H1: Multi-Function Contact Inputs

u
H1-01 to H1-07: Functions for Terminals S1 to S7
n
These parameters assign functions to the seven multi-function contact inputs located at terminals S1 through S7. Settings 0 to 9F determine the type of
input for each terminal.
Note: If not using an input terminal or if using the through-mode, set that terminal to "F".
No.
Parameter Name
H1-01
Multi-Function Digital Input Terminal S1 Function Selection
H1-02
Multi-Function Digital Input Terminal S2 Function Selection
H1-03
Multi-Function Digital Input Terminal S3 Function Selection
H1-04
Multi-Function Digital Input Terminal S4 Function Selection
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
*Number appearing in parenthesis is the default value after performing a 3-wire initialization.
Setting
0
3-Wire Sequence
1
LOCAL/REMOTE Selection
2
Option/Drive Selection
3
Multi-Step Speed Reference 1
8
Baseblock Command (N.O.)
9
Baseblock Command (N.C.)
A
Accel/Decel Ramp Hold
B
Drive Overheat Alarm (OH2)
C
Terminal A2 Enable
F
Not used
10
Up Command
11
Down Command
12
Forward Jog
13
Reverse Jog
14
Fault Reset
15
Fast-Stop (N.O.)
16
Motor 2 Selection
17
Fast-stop (N.C.)
18
Timer Function
19
PID Disable
1A
Accel/Decel Time Selection 2
1B
Program Lockout
1E
Reference Sample Hold
20 to 2F
External Fault
30
PID Integral Reset
31
PID Integral Hold
32
Multi-Step Speed Reference 4
34
PID Soft Starter
35
PID Input Switch
Detailed Description
Setting 0: 3-Wire Sequence
When one of the digital inputs (S3 to S7) is programmed for 3-wire control, that input becomes a forward/reverse directional input. Whenever the input
is open, the drive will be set for forward rotation of the motor shaft. If the input it closed, then the motor shaft will rotate in the reverse direction whenever
a there is a run command entered.
Note: The run and stop commands are allotted to terminals S1 and S2.
160
Table 5.15 Multi-Function Contact Input Settings
Function
Page
Setting Range
1 to 9F
40: Forward Run Command (2-wire sequence)
1 to 9F
41: Reverse Run Command (2-wire sequence)
0 to 9F
24: External Fault (user selection possible)
14: Fault Reset
0 to 9F
Closed: Allows the drive to run again after the fault is cleared and the run command is
removed
0 to 9F
3 (0)
*
: Multi-Step Speed Reference 1
0 to 9F
*
4 (3)
: Multi-Step Speed Reference 2
6 (4)
*
: Jog Reference Selection
0 to 9F
Takes priority over other multi-step speed references 1 through 16
Setting
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 2
6
Jog Reference Selection
7
Accel/Decel Time 1
40
Forward Run Command (2-wire sequence)
41
Reverse Run Command (2-wire sequence)
42
Run Command (2-wire sequence 2)
43
FWD/REV Command (2-wire sequence 2)
44
Offset Frequency 1 Addition
45
Offset Frequency 2 Addition
46
Offset Frequency 3 Addition
60
DC Injection Braking Command
61
External Search Command 1
62
External Search Command 2
65
KEB Ride-Thru (N.C.)
66
KEB Ride-Thru (N.O.)
67
Communications Test Mode
68
High-Slip Braking
6A
Drive Enable
75
Up 2 Command
76
Down 2 Command
7A
KEB Ride-Thru 2 (N.C.)
7B
KEB Ride-Thru 2 (N.O.)
7C
Short-Circuit Braking (N.O.)
7D
Short-Circuit Braking (N.C.)
7E
Forward/Reverse Detection (Simple PG in V/f)
90 to 96
DriveWorksEZ Digital Input 1 to 7
9F
DriveWorksEZ Digital Input 9F
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)