8.
Press
to save the setting.
9.
The display will return to the screen shown in step 4.
10.
Press
until the display returns to the first screen.
• Switch between LOCAL and REMOTE using parameters b1-01 and b1-02:
This method can be used to issue the frequency reference from the operator keypad and the Run command from the control terminals.
o2-02: STOP Key Function Selection
n
The STOP key is enabled during Auto Run as a default, which enables the STOP key on the digital operator even if b1-02 has assigned the Run command
to be given from a remote source (i.e., not from the operator). In effect, the STOP key becomes an alternative stop input. Once the drive has been stopped
by the STOP key, it can be restarted by cycling the external Run command. If o2-02 = "0: Disabled", then pressing the STOP key while the drive is set
for REMOTE will have no effect.
No.
Parameter Name
o2-02
STOP Key Function Selection
o2-03: User Parameter Default Value
n
The drive gives the option of configuring any and all of the programming parameters and then saving the parameters as "User Initialization Values". After
configuring the drive, set parameter o2-03 = "1: Set Defaults" to save the parameters to the User Initialization memory. Once this has been done, the
"Initialize Parameters" parameter (A1-03) will offer the choice of "1110: User Initialize". Choosing A1-03 = "1110: User Initialized", will reset all
modified parameters back to what they were the last time they were saved using o2-03.
No.
Parameter Name
o2-03
User Parameter Default Value
o2-04: Drive/kVA Selection
n
Parameter o2-04 matches the control board to the drive hardware. Proper setting of o2-04 is important so that the control board can provide proper protection
for the drive hardware. This parameter is configured at the factory and does not normally require adjustment in the field. It is available primarily to
accommodate control board replacement in the event of damage.
No.
Parameter Name
o2-04
Drive/kVA Selection
Note: The default settings for some parameters are determined by the capacity of the drive set to o2-04.
An oPE04 error will occur if someone attempts to install a removable terminal board and control board to drive that has a different capacity from the
capacity saved to memory of those boards. The oPE04 error indicates that the terminal board doesn't match the control board. To reset oPE04, the drive
needs to be initialized by using parameter A1-03. To reset the oPE04 error without initializing any parameter settings, set 5550 to A1-03. Otherwise,
initialize the entire drive with a 2-wire or a 3-wire initialization (settings 2220 and 3330 respectively).
Note: Drive performance will suffer If the correct drive capacity is not set to o2-04, and protective functions will fail to operate properly.
o2-05: Frequency Reference Setting Method Selection
n
Determines if the ENTER key must be used to input a frequency reference from the digital operator.
No.
Parameter Name
o2-05
Frequency Reference Setting Method Selection
The default setting of the Frequency Reference Setting Method parameter (o2-05 = "1: Enabled") dictates that when setting a frequency reference via the
digital operator (LOCAL), it is not necessary to press the "ENTER" key before the drive will begin to accelerate or decelerate to the new set speed. When
o2-05 = "1: Enabled", the frequency reference is stored to memory five seconds after the up arrow or down arrow keys are released.
o2-06: Operation Selection when Digital Operator is Disconnected
n
Determines if the drive will stop when the LCD operator is removed in LOCAL mode or with b1-02 set to 0.
No.
Parameter Name
o2-06
Operator is Disconnect Operation
Note: An LCD operator is available as an option. This setting is not applicable to the standard LED operator that comes with the drive.
o2-07: Motor Direction at Power Up when Using Operator
n
Determines the direction the motor will rotate after the drive is powered up when the Run command is set to be given from the LED operator.
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Step
0: Disabled
1: Enabled
0: No Change
1: Set Defaults - Saves current parameter settings as user initialization.
2: Clear All - Clears the currently saved user initialization.
Sets the kVA of the drive. This parameter only needs to be set when installing a new control
board. Do not change for any other reason.
0: ENTER key required.
1: ENTER not required.
0: Disabled. Drive does not stop when the digital operator is removed.
1: Enabled. The drive will fault (OPR) and coast to stop when the digital operator is removed.
5.10 o: Digital Operator Related Settings
Display/Result
Setting Range
Setting Range
Setting Range
Setting Range
Setting Range
Default
1
Default
0
Default
Determined by
o2-04
Default
0
5
Default
0
207