Advertisement

5.1 A: Initialization
4.
Press
to return to the first screen.
The following procedure shows how to displays the password, continuing from step 4 above.
1.
Press
to display the screen for parameter setup.
2.
Press
to select the flashing digits as shown.
3.
Press
to scroll to A1-04.
4.
Enter the password "1234".
5.
Press
to save the new password.
6.
Screen returns to the parameter display.
7.
Press
and scroll to A1-02.
8.
Press
to display the value set to A1-02.
9.
Use
and
to set the desired value.
10.
Press
to save the setting.
11.
The display automatically returns to the parameter display.
Note: Parameter settings may be edited after entering the correct password. Performing a 2-wire or 3-wire initialization resets the password to "0000". Re-enter the password after
drive initialization.
Note: To change the password, enter the new password to parameter A1-05.
A1-06: Application Presets
n
To make it easier to set up the drive for commonly used applications, there are several Application Presets available. By selecting one of these presets,
the drive automatically sets the required parameters to their optimal values for that specific application. To further customize these settings, the user can
still make changes using the Setup Mode.
No.
Parameter Name
A1-06
Application Presets
By selecting one of the application presets, I/O terminal settings are changed from their default values and assigned functions appropriate for the application that was
Perform a 2-wire or 3-wire initialization (A1-03 = 2220 or 3330) on the drive before selecting an Application Preset.
Note: Do not switch between Application Presets without performing a 2-wire or 3-wire initialization (A1-03 = 2220 or 3330) prior to changing the application selected. Drive
parameters should be fully reset by the initialization process before using one of the Application Presets.
Note: Parameters edited by the user can be saved to a list by setting o2-03 to 1. This allows for more immediate access a specific list of relevant parameters, and saves time scrolling
through the parameter menu items.
Note: To allow only the Setup Parameters to be displayed, set the parameter access level for Preferred Parameters (A1-01 = 1).
The parameters listed in the table below are unaffected when the drive is initialized:
No.
A1-02
*
C6-01
E1-03
E5-01
104
Step
Step
0: Disabled
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Compressor
6: Crane (hoist)
7: Crane (traverse)
The next procedure sets the drive for a water supply pump application
selected. Verify all I/O signals and external sequences before operating the motor.
When A1-06 = 0, all general-use parameters are accessible.
Setting Range
A1-06 = 1
Parameter Name
Control Method Selection
Duty Selection
V/f Pattern Selection
Motor Code Selection (for PM motors)
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Display/Result
Display/Result
"01 flashes
"0" flashes
Open Loop Vector Control
Default
0