Note: IP20/NEMA Type 1 and IP20/Open-Chassis models require the same amount of space above and below the drive for installation.
Multiple Drive Installation
n
When installing multiple drives into the same enclosure panel, mount the drives according to
by-side clearance of 2 mm according to
293.
A
Note: When installing drives of different sizes into the same enclosure panel, the tops of the drives should line up. Leave space between the top and bottom of stacked drives for
cooling fan replacement if required. Using this method, it is possible to replace the cooling fans later.
NOTICE: When drives with IP20/NEMA Type 1 enclosure are mounted side by side, the top covers of all units must be removed as shown in
u

Removing and Attaching the Protective Covers

Refer to Electrical Installation on page

Exterior and Mounting Dimensions

u
The table below matches each drive model with its appropriate drawing.
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Side Clearance
A
A
A – 30 mm minimum
B – Airflow direction
Figure 2.2 Correct Installation Spacing
Figure 2.3
, derating must be considered and parameter L8-35 must be set.
B
2 mm
A – Line up the tops of the drives.
B – 30 mm minimum
Figure 2.3 Space Between Drives (Side-by-Side Mounting)
Figure 2.4 IP20/NEMA 1 Side-by-Side Mounting in Enclosure
31, for information regarding the removal and reattachment of protective covers.
Top/Bottom Clearance
C
B
C
C – 100 mm minimum
Figure 2.2
B
C
C
C – 100 mm minimum
D – Airflow direction
2.2 Mechanical Installation
. When mounting drives with a minimum side-
Refer to Parameter List on page
D
Figure 2.4
.
2
27