YASKAWA V1000 Series Technical Manual page 299

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

No.
Name
C2-01
S-Curve Characteristic at Accel Start
C2-02
S-Curve Characteristic at Accel End
C2-03
S-Curve Characteristic at Decel Start
C2-04
S-Curve Characteristic at Decel End
C3-01
Slip Compensation Gain
<22>
Slip Compensation Primary Delay
C3-02
Time
C3-03
Slip Compensation Limit
Slip Compensation Selection during
C3-04
Regeneration
Output Voltage Limit Operation
C3-05
Selection
C4-01
Torque Compensation Gain
<23>
Torque Compensation Primary Delay
C4-02
Time
Torque Compensation at Forward
C4-03
Start
Torque Compensation at Reverse
C4-04
Start
Torque Compensation Time Constant Sets the time constant for torque compensation at forward start and reverse
C4-05
Torque Compensation Primary Delay
C4-06
Time 2
C5-01
ASR Proportional Gain 1
<22>
C5-02
ASR Integral Time 1
<22>
C5-03
ASR Proportional Gain 2
<22>
C5-04
ASR Integral Time 2
<22>
C5-05
ASR Limit
<22>
C6-01
Normal/Heavy Duty Selection
C6-02
Carrier Frequency Selection
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Description
C2: S-Curve Characteristics
Use C2 parameters to configure S-curve operation.
The S-curve can be controlled in the four points shown below.
run
command
ON
OFF
output
frequency
C2-02
C2-03
C2-01
C2-04
time
S-curve is used to further soften the starting and stopping ramp. The longer
the S-curve time, the softer the starting and stopping ramp.
C3: Slip Compensation
Use C3 parameters to configure the slip compensation function.
Sets the slip compensation gain. Decides for what amount the output
frequency is boosted in order to compensate the slip.
Note: Adjustment is not normally required.
Adjusts the slip compensation function delay time.
Decrease the setting when the slip compensation response is too slow, increase
it when the speed is not stable.
Disabled when Simple V/f Control with PG (H6-01 = 3) is used.
Sets the slip compensation upper limit. Set as a percentage of motor rated slip
(E2-02). Disabled when Simple V/f Control with PG (H6-01 = 3) is used.
Selects slip compensation during regenerative operation.
0: Disabled
1: Enabled
Using the Slip Compensation function during regeneration may require a
braking option to handle momentary increasing regenerative energy.
Selects if the motor magnetic flux is reduced during output voltage saturation.
0: Disabled
1: Enabled
C4: Torque Compensation
Use C4 parameters to configure Torque Compensation function.
V/f control: Sets the gain for the automatic torque (voltage) boost function
and helps to produce better starting torque.
Increase this setting when using a long motor cable or when the motor is
significantly smaller than the drive capacity.
Decrease this setting when motor oscillation occurs. Set the value so that the
current at low speed does not exceeds the drives rated current.
Open Loop Vector: Sets the torque compensation function gain. Normally no
change is required.
Sets the torque compensation filter time.
Increase this setting when motor oscillation occurs.
Reduce the setting if there is not enough response from the motor.
Sets torque compensation at forward start as a percentage of motor torque.
Sets torque compensation at reverse start as a percentage of motor torque.
start (C4-03 and C4-04). The filter is disabled if the time is set to 4 ms or less.
Sets the torque compensation time 2. When an OV fault occurs with sudden
load changes or at the and of an acceleration, increase the setting.
Note: Adjustment is not normally required. If adjusted then AFR time 2
(n2-03) should be adjusted too.
C5: Speed Control (ASR)
Use C5 parameters to configure the Automatic Speed Regulator (ASR).
C5 parameters are available only when using V/f with Simple PG (H6-01 = 3).
Sets the proportional gain of the speed control loop (ASR).
Sets the integral time of the speed control loop (ASR).
Sets the speed control gain 2 of the speed control loop (ASR).
Sets the integral time 2 of the speed control loop (ASR).
Sets the upper limit for the speed control loop (ASR) as a percentage of the
maximum output frequency (E1-04).
C6: Carrier Frequency
Use C6 parameters to configure the carrier frequency drive settings.
Selects the load rating for the drive.
0: Heavy Duty (HD) for constant torque applications.
1: Normal Duty (ND) for variable torque applications.
This setting affects the Rated output current and overload tolerance of the
drive.
Selects the carrier frequency
1 : 2.0 kHz
2 : 5.0 kHz
3 : 8.0 kHz
4 : 10.0 kHz
5 : 12.5 kHz
6 : 15.0 kHz
7 : Swing PWM1 (Audible sound 1)
8 : Swing PWM2 (Audible sound 2)
9 : Swing PWM3 (Audible sound 3)
A : Swing PWM4 (Audible sound 4)
B to E: No setting possible
F : User defined (determined by C6-03 through C6-05)
B.2 Parameter Table
Control
Mode
Range
Def.
V/f OL V PM
0.20 s
0.00 to 10.00
A
A
A
<2>
0.00 to 10.0
0.20 s
A
A
A
0.00 to 10.0
0.20 s
A
A
A
0.00 to 10.0
0.00 s
A
A
A
0.0 to 2.5
0.0
A
A
<2>
2000 ms
0 to 10000
A
A
<2>
0 to 250
200%
A
A
0, 1
0
A
A
0, 1
0
A
<2>
0.00 to 2.50
1.00
A
A
A
200 ms
0 to 60000
A
A
A
<1>
0.0 to 200.0
0.0%
A
-200.0 to 0.0
0.0%
A
0 to 200
10 ms
A
0 to 10000
150 ms
A
0.00 to 300.00
0.20
A
0.000 to 10.000
0.200 s
A
0.00 to 300.00
0.02
A
0.000 to 10.000
0.050 s
A
0.0 to 20.0
5.0%
A
0, 1
1
S
S
S
1 to F
S
S
S
<3>
Addr.
Pg.
Hex
20B
20C
20D
20E
20F
210
211
212
213
215
216
217
218
219
21AH
21B
21C
21D
21E
21F
223
82
82
224
B
299

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents