D: References; D: References; D1: Frequency Reference; D2: Frequency Upper/Lower Limits - YASKAWA Z1000U Series Programming Manual

Hvac matrix low harmonic drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

A.6 d: References
A.6 d: References
Reference parameters set the various frequency reference values during operation.
u

d1: Frequency Reference

No.
(Addr.
Name
Hex)
d1-01
(0280)
Frequency Reference 1 Reference 1
d1-02
(0281)
Frequency Reference 2 Reference 2
d1-03
(0282)
Frequency Reference 3 Reference 3
d1-04
(0283)
Frequency Reference 4 Reference 4
d1-16
(0291)
Frequency Reference 16 Reference 16
d1-17
Jog Frequency
(0292)
Reference
<1> Range upper limit is determined by parameters d2-01, Frequency Reference Upper Limit, and E1-04, Maximum Output Frequency.
u

d2: Frequency Upper/Lower Limits

No.
(Addr.
Name
Hex.)
d2-01
Frequency Reference
(0289)
Upper Limit
d2-02
Frequency Reference
(028A)
Lower Limit
d2-03
Master Speed Reference
(0293)
Lower Limit
204
LCD Display
Sets the frequency reference for the drive. Setting units are
determined by parameter o1-03.
Sets the frequency reference for the drive. Setting units are
determined by parameter o1-03.
Sets the frequency reference for the drive. Setting units are
determined by parameter o1-03.
Sets the frequency reference for the drive. Setting units are
determined by parameter o1-03.
Sets the frequency reference for the drive. Setting units are
determined by parameter o1-03.
Sets the Jog frequency reference. Setting units are determined
by parameter o1-03.
Jog Reference
LCD Display
Sets the frequency reference upper limit as a percentage of the
Ref Upper Limit
maximum output frequency.
Sets the frequency reference lower limit as a percentage of the
Ref Lower Limit
maximum output frequency.
Sets the lower limit for frequency references from analog inputs
Ref1 Lower Limit
as a percentage of the maximum output frequency.
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
Description
Description
Values
Page
Default: 0.00 Hz
Min.: 0.00
52
Max.: 400.00
<1>
Default: 0.00 Hz
Min.: 0.00
52
Max.: 400.00
<1>
Default: 0.00 Hz
Min.: 0.00
52
Max.: 400.00
<1>
Default: 0.00 Hz
Min.: 0.00
52
Max.: 400.00
<1>
Default: 0.00 Hz
Min.: 0.00
52
Max.: 400.00
<1>
Default: 6.00 Hz
Min.: 0.00
52
<1>
Max.: 400.00
Setting
Page
Default: 100.0%
Min.: 0.0
53
Max.: 110.0
Default: 0.0%
Min.: 0.0
53
Max.: 110.0
Default: 0.0%
Min.: 0.0
54
Max.: 110.0