B.2 Parameter Table
No.
H2-06
Watt Hour Output Unit Selection
<40> The availability of certain functions depends on the control method used.
H2-oo
Function
Setting
0
During Run
1
Zero Speed
2
Fref/Fout Agree 1
3
Fref/Fset Agree 1
4
Frequency (FOUT) Detection 1
5
Frequency (FOUT) Detection 2
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock
9
Option Reference
A
Local/Remote
B
Torque Detection 1 (N.O.)
C
Loss of Reference
D
Braking Resistor Fault
E
Fault
F
Not used
10
Alarm
11
Reset Command Active
12
Timer Output
13
Fref/Fout Agree 2
14
Fref/Fset Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
18
Torque Detection 2 (N.O.)
19
Torque Detection 2 (N.C.)
1A
Reverse Direction
1B
Baseblock 2
1C
Motor 2 Selection
1E
Restart Enabled
1F
Overload Alarm OL1
20
OH Pre alarm
22
Mechanical Weakening (N.O.)
30
During Torque Limit
37
During Frequency Output
38
Drive Enable
39
Watt Hour Pulse Output
3C
Drive Mode
3D
Speed Search
3E
PID Feedback Loss
3F
PID Feedback Fault
4A
KEB Operation
4B
Short-Circuit Brake
4C
During Fast-stop
4D
OH Pre-alarm Time Limit
308
Name
Sets the display units for one of the multi-function output
terminals that is assigned to output the watt hours (H2-
39) is the value every 200 ms. An output pulse of 200 ms is
provided for every kWh that occurs. Intended to drive a
counter, meter or PLC for logging kWh.
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
H2 Multi-Function Digital Output Settings
Closed: A Run command is active or voltage is output.
Closed: Output frequency is 0.
Closed: Output frequency equals the speed reference (plus or minus the hysteresis set to L4-02).
Closed: Output frequency and speed reference equal the value in L4-01 (plus or minus the hysteresis of L4-02). O
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis determined by L4-02.
Closed: Output frequency is greater than or equal to the value in L4-01, with hysteresis determined by L4-02.
Closed: Drive Ready. The drive is powered up, not in a fault state, and in the Drive mode.
Closed: DC bus voltage is below the UV trip level set in L2-05.
Closed: This is no output voltage
Closed: Digital operator supplies the frequency reference.
Open: Reference 1 or 2 are active
Closed: Digital operator supplies the run command.
Closed: Output current/torque exceeds the torque value set in parameter L6-02 for longer than the time set in
parameter L6-03.
Closed: Loss of the analog frequency reference detected. Enabled when L4-05 = 1.
Closed: Braking resistor or transistor is overheated or faulted out. This selection requires that braking resistor
protection parameter be set for ERF (L8-01 = "1").
Closed: Fault occurred (other than CPF00 and CPF01).
Set this value when the terminal is not used, or when using the terminal in the pass-through mode.
Closed: An alarm is triggered.
Closed: Reset command to the drive is active.
Timer output, controlled by b4-01 and b4-02. Used in conjunction with the digital input (H1-oo = 18 "timer
function").
Closed: When drive output frequency equals the frequency reference +/- L4-04.
Closed: When the drive output frequency is equal to the value in L4-03 (plus or minus L4-04).
Closed: When the drive output frequency is less than or equal to the value in L4-03 with the hysteresis determined
by L4-04.
Closed: When the output frequency is greater than or equal to the value in L4-03 with the hysteresis determined
by L4-04.
Open: When the output current/torque exceeds the value set in parameter L6-02 for more time than is set in
parameter L6-03.
Closed: When the output current/torque exceeds the value set in parameter L6-05 for more time than is set in
parameter L6-06.
Open: Output current/torque exceeds the value set in parameter L6-05 for more time than is set in parameter
L6-06.
Closed: Drive is running in the reverse direction.
Open: Drive is in base block condition. Output is disabled.
Closed: Motor 2 is selected by a digital input (H1-oo = 16)
Closed: An automatic restart is performed
Closed: OL1 is at 90% of its trip point or greater.
Closed: Heatsink temperature exceeds the parameter L8-02 value.
Closed: Mechanical Weakening detected.
Closed: When the torque limit has been reached.
Closed: Frequency is output
Open: Operation stopped, Baseblock, DC Injection Braking, or Initial Excitation is being performed.
Closed: Multi-function input closes (H1-oo = 6A)
Output units are determined by H2-06, outputs 200 ms pulse for each incremented kWh count.
Closed: Local
Open: Remote
(this signal combines setting values 9 and A)
Closed: Speed search is being executed.
Closed: PID Feedback Loss.
PID feedback value is below the level set to b5-13 for longer than the time set in b5-14.
Closed: PID Feedback Fault.
PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37.
Closed: KEB is being performed.
Closed: Short-Circuit Braking is active.
Closed: Fast-stop command is entered
Closed: OH Pre-alarm time limit is passed.
Description
=
Description
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Control
Mode
Range
Def.
V/f OL V PM
0 to 4
0
A
A
A
Control
Mode
V/f OL V PM
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
Addr.
Pg.
Hex
437
Pg.
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents