When setting the frequency by analog reference from an external potentiometer, use shielded twisted-pair wires and ground the shield of twisted-pair
wires to the ground terminal of the drive.
NOTICE: The analog signal lines between the drive and the operator station or peripheral equipment should not exceed 50 meters when using an analog signal from a remote
source to supply the frequency reference. Failure to comply could result in poor system performance.
Figure 3.24 Wiring the Frequency Reference to the Control Circuit Terminals (External Reference)
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
A
C
A – Control terminal block
B – Avoid fraying wire strands when
stripping insulation from wire. Strip
length 5.5 mm.
C – Single wire or stranded wire
Figure 3.22 Terminal Board Wiring Guide
F
A
B
A – Drive side
B – Connect shield to ground terminal of
drive.
C – Insulation
Figure 3.23 Preparing the Ends of Shielded Cables
2 k
G
A – Drive
B – Ground terminal (shield connection)
C – (RP) Pulse train (maximum 32 kHz)
D – (+V) Frequency setting power source
+10.5 Vdc maximum 20 mA
D
Preparing wire
E
terminal ends
B
D – Loosen screw to insert wire.
E – Blade depth of 0.4 mm or less
Blade width of 2.5 mm or less
C
D
E
D – Control device side
E – Shield sheath (Insulate with tape)
F – Shield
A
B
C
RP
D
+V
E
A1
F
A2
AC
E – (A1) Main speed frequency reference
0 to +10 Vdc (20 kΩ)
F – (A2) Multi-function analog input
0 to +10 Vdc (20 kΩ) or
4 to 20 mA (250 Ω)/
0 to 20 mA (250 Ω)
G – Frequency setting potentiometer
3.7 Control Circuit Wiring