No.
E1-12
Mid Output Frequency Voltage 2
E1-13
Base Voltage (VBASE)
*1. Values shown here are for 200 V class drives. Double the value when using a 400 V class unit.
*2. Default setting is determined by the control mode (value shown here is for V/f Control).
*3. Default setting varies based on the V/f pattern set to E1-03.
*4. When using PM Open Loop Vector, the default setting is determined by the motor code set to E5-01.
Setting Instructions
1. Set the input voltage for the drive. For instructions, see page 133.
2. Choose one of the two following V/f patterns:
Select one of the 15 preset V/f patterns (setting = 0 through E)
Custom V/f pattern (setting = F)
3. When using one of the preset patterns, the parameters listed below are set automatically.
When using a custom V/f pattern, set these parameters as desired:
E1-04 (Max Output Frequency), E1-05 (Max Voltage), E1-06 (Base Frequency), E1-07 (Mid Output Frequency, E1-08 (Mid Output Frequency Voltage),
E1-09 (Min Output Frequency), E1-10 (Min Output Frequency Voltage)
4. Settings for the E1 parameters are determined by drive capacity. Drive capacities are divided into the two following ranges:
V/f pattern for 0.1 to 3.7 kW drives
V/f pattern for 5.5 to 18.5 kW drives
The user can select one of 15 preset V/f patterns (setting = 0 through E) or decide to set a customized V/f pattern (setting = F). By selecting one of the 15
presets (settings 0 through E), the drive will automatically set the parameters listed in the table below.
E1-09 less than or equal to E1-07 less than or equal to E1-06 less than or equal to E1-11 less than or equal to E1-04
Note: When the drive is initialized using parameter A1-03, the setting of E1-03 is unaffected but the settings of E1-04 through E1-13 are returned to their default settings.
V/f Patterns for 0.1 to 3.7 kW Drives
The following graphs are for 200 V class drives. Double values when using a 400 V class unit.
Setting = 0
50 Hz
200
16
12
0
1.3 2.5
50
Frequency (Hz)
Setting = 4
50 Hz
200
35
8
0
1.3
25
50
Frequency (Hz)
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Name
Output Voltage (V)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
Figure 5.35 V/f Pattern
Table 5.5 Constant Torque Characteristics, Settings 0 to 3
Setting = 1
60 Hz
200
16
12
0
1.5 3
60
Frequency (Hz)
Table 5.6 Derated Torque Characteristics, Settings 4 to 7
Setting = 5
50 Hz
200
50
9
0
1.3
25
50
Frequency (Hz)
Setting Range
0.0 to 255.0 *1
0.0 to 255.0 *1
Setting = 2
60 Hz
200
16
12
0
1.5 3
50
60
Frequency (Hz)
Setting = 6
60 Hz
200
35
8
0
1.5
30
60
Frequency (Hz)
5.5 E: Motor Parameters
Default
0.0 V
0.0 V
Setting = 3
72 Hz
200
16
12
0
1.5 3
60
72
Frequency (Hz)
Setting = 7
60 Hz
200
50
9
0
1.5
30
60
Frequency (Hz)
147