C.7 Enter Command
C.7

Enter Command

When writing parameters to the drive from the PLC using MEMOBUS/Modbus communication, the parameters are temporarily stored in the parameter
data area of the drive. To enable these parameters in the parameter data area, the Enter command must be used.
There are two types of Enter commands: Enter commands that enable parameter data in RAM only (changes are lost when the drive is shut off), and Enter
commands that write data into the EEPROM (non-volatile memory) of the drive and enable the data in RAM at the same time.
The following table shows the Enter command data. The Enter command is enabled by writing 0 to register number 0900H or 0910H.
Register No.
0900H
0910H
Note: Because the EEPROM can be written to a maximum of 100,000 times, refrain from writing to the EEPROM too often. The ENTER command registers are write-only.
Consequently, if these registers are read, then the register address will be invalid (Error code: 02H). An ENTER command is not required if reference or broadcast data are
sent to the drive.

ENTER Command Settings when Upgrading the Drive

u
To transfer parameter settings from an earlier Yaskawa model drive to V1000, parameter H5-11 needs to be set in accordance with how the Enter command
functions in the older drive.
If upgrading from a G7 or F7 series drive to V1000, set parameter H5-11 to 0.
If upgrading from a V7 series drive to V1000, set parameter H5-11 to 1.
No.
Name
Communications ENTER
H5-11
Function Selection
Note: Option cards are designed for a specific model, and are not compatible between drives.
H5-11 and the Enter Command
n
H5-11 Settings
Drive being replaced
How parameter settings are enabled
Upper/Lower limit check
Default value of related parameters
Error when setting multiple parameters
Operation when saving several parameter settings at once Allows all valid settings to be saved
340
Saves parameter data to EEPROM
Updates parameter data to RAM without saving to EEPROM
Description
Select the function for the enter command that saves parameter data to
the drive.
0: Save parameter data that was edited to the drive when the enter
command is given.
1: Parameter data that has been edited is saved when the enter command
is given (compatible with the V7).
G7, F7
When the ENTER key is pressed
Determined by related parameters
Not affected
Data is accepted even if one setting is invalid
Description
Setting
0.1
H5-11 = 0
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Control Mode
Default
VF
OLV
1
A
A
H5-11 = 1
V7
As soon as the value is changed
Single upper/lower limit
Determines the default values of related parameters
Error occurs if one setting is invalid
No data is written if a single piece of data is invalid
Addr. Hex
PM
A