5.4 d: Reference Settings
d2-03: Master Speed Reference Lower Limit
n
Unlike frequency reference lower limit (d2-02) which will affect the frequency reference no matter where it is sourced from (i.e., analog input, preset
speed, Jog speed, etc.), the frequency reference lower limit (d2-03) sets a low speed threshold that will only affect the analog input (terminals A1 and A2)
that is the active master speed frequency.
Set as a percentage of the maximum output frequency.
Note: The lower limits for the Jog frequency, multi-step speed settings, and 2-step speed settings do not change. When lower limits are set to both the frequency reference (d2-02)
and the main frequency reference (d2-03), the drive uses the greater of those two values as the lower limit.
No.
d2-03
u

d3: Jump Frequency

d3-01 to d3-04: Jump Frequencies 1, 2, 3
n
d3-04: Jump Frequency Width
n
In order to avoid continuous operation at a speed that causes resonance in driven machinery, the drive can be programmed with Jump Frequencies that
will not allow continued operation within specific frequency ranges. If a speed is commanded that falls within a dead band, or Jump Frequency, the drive
will clamp the frequency reference just below the dead band and only accelerate past it when the commanded speed rises above the upper end of the dead
band, for increasing references.
No.
d3-01
d3-02
d3-03
d3-04
Detailed Description
The figure below shows the relationship between the Jump Frequency and the output frequency.
Note: The drive will not operate within the specified deadband range for the Jump Frequency. Although the drive quickly accelerates (or decelerates) the motor through the Jump
Frequency frequency range, it still maintains the accel/decel times sets to C1-01 and C1-02. When using more than one Jump Frequency, make sure that d3-01 is greater than
or equal to d3-02 is greater than or equal to d3-03. Setting parameters d3-01 to d3-03 to 0 essentially disables the Jump Frequency.
u

d4: Frequency Reference Hold

Determines how bias values affect the frequency reference, and also whether or not the frequency reference is saved when the power is shut off.
d4-01: Frequency Reference Hold Function Selection
n
This function is available when the multi-function inputs "accel/decel ramp hold" or "Up/Down" commands are selected (H1-oo = A or 10 and 11).
Determines whether or not the frequency reference is saved when the power supply is shut off.
No.
d4-01
Detailed Description
0
Disabled: Starts the motor from 0.
142
Parameter Name
Master Speed Reference Lower Limit
Parameter Name
Jump Frequency 1
Jump Frequency 2
Jump Frequency 3
Jump Frequency Width
Output
Frequency
Jump
Frequency
Width (d3-04)
Jump
Frequency 3
d3-03
Parameter Name
Frequency Reference Hold Function Selection
Setting Range
0.0 to 110.0
Setting Range
0.0 to 400.0
0.0 to 20.0
frequency
reference
frequency
decreases
reference
increases
Jump
Frequency
Width (d3-04)
Jump
Frequency
Width (d3-04)
Jump
Jump
Frequency 2
Frequency 1
d3-02
d3-01
Setting Range
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Default
Default
Frequency
Reference
Default
0, 1
0.0%
0.0 Hz
0.0 Hz
0.0 Hz
1.0 Hz
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents