H6-01: (Terminal RP) Pulse Train Input Function Selection
n
Selects the function of pulse train (terminal RP).
This parameter selects the function of the pulse train terminal RP. If pulse train is to be used as the frequency reference (H6-01 = 0) parameter b1-01 must
be set to "4: Pulse Input."
No.
Parameter Name
H6-01
(Terminal RP) Pulse Train Input Function Selection
H6-02: Pulse Train Input Scaling
n
Pulse train input scaling parameter sets the number of pulses (in Hz) that is equal to the maximum output frequency E1-04.
No.
H6-02
H6-03: Pulse Train Input Gain
n
Pulse train input gain sets the output level with the pulse train input is at 100% as a percentage of maximum output frequency (E1-04).
No.
H6-03
H6-04: Pulse Train Input Bias
n
Pulse train input bias sets the output level when the pulse train input is 0 Hz as a percentage of maximum output frequency (E1-04).
No.
H6-04
H6-05: Pulse Train Input Filter Time
n
Sets the pulse train input filter time constant in seconds.
No.
H6-05
H6-06: Pulse Train Input Monitor Selection
n
Selects the pulse train monitor output terminal MP function (value of the oo part of monitor U1-oo). See Appendix A for a complete list of monitors.
No.
H6-06
Pulse Train Input Monitor Selection
H6-07: Pulse Train Input Monitor Scaling
n
Pulse train monitor scaling sets the number of output pulses when the monitor is 100% (in Hz). Set H6-06 to 102 and H6-07 to 0 to make the pulse train
monitor output synchronous to the output frequency.
No.
H6-07
Pulse Train Input Monitor Scaling
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
0: Frequency reference
1: PID feedback value
2: PID setpoint value
3: Simple PG V/f control mode (can be set only when using motor 1 in the V/f control mode)
Parameter Name
Pulse Train Input Scaling
Parameter Name
Pulse Train Input Gain
Parameter Name
Pulse Train Input Bias
Parameter Name
Pulse Train Input Filter Time
Parameter Name
Parameter Name
Setting Range
Setting Range
1000 to 32000
Setting Range
0.0 to 1000.0
Setting Range
-100.0 to 100.0
Setting Range
0.00 to 2.00
Setting Range
000, 031, 101, 102, 105, 116, 501, 502, 801 to 809
Setting Range
0 to 32000
5.7 H: Terminal Functions
Default
0
Default
1440 Hz
Default
100.0%
Default
0.0%
Default
0.10 s
Default
102
Default
1440 Hz
185
5