5.7 H: Terminal Functions
Status
Open
Closed
Setting 38: Drive Enabled
A Drive Enable digital output will reflect the status of a digital input configured as a Drive Enable input (H1-0x = 6A). If the Drive Enable digital input
is closed then the Drive Enabled digital output will also close.
Setting 39: Watt Hour Pulse Output
Outputs a pulse to indicate the watt hour. Set H2-06 to specify the units. Output terminal closes every 200 ms.
No.
H2-06
Watt Hour Output Unit Selection
Setting 3C: REMOTE/LOCAL Switch
Output terminal closes while the drive is set for LOCAL, and opens when in REMOTE.
Status
Open
Closed
Setting 3D: During Speed Search
Output terminal closes while Speed Search is being performed.
Setting 3E: PID Feedback Loss
Output terminal closes when a the PID feedback signal is lost. Works for both pulse input and analog input PID signals. For PID loss to be detected, set
the loss level to b5-13 and the detection time to b5-14.
No.
b5-13
PID Feedback Loss Detection Level
b5-14
PID Feedback Loss Detection Time
Note: For details on a PID,
b5: PID
Setting 3F: PID Feedback High Fault
Output terminal closes when a the PID feedback signal is too high for too long. Works for both pulse input and analog input PID signals. To detect an
excessively high PID signal, set the detection level to b5-36 and the detection time to b5-37.
No.
b5-36
PID Feedback High Detection Level
b5-37
PID Feedback High Level Detection Time
Note: For details on a PID,
b5: PID
Setting 4A: During KEB Operation
Output terminals closes while KEB is being performed.
Setting 4B: During Short Circuit Braking
Closes the output terminal while Short Circuit Braking is being executed.
Setting 4C: During Fast Stop
Output terminal closes when a Fast Stop is being executed.
Setting 4D: oH Pre-Alarm Time Limit
Output terminals closes when then overheat prealarm continues passed the allowable time.
178
Drive is stopped or is performing DC Injection, Short Circuit Braking, or Initial Excitation.
OFF
ON
run command
baseblock
OFF
command
output
frequency
OFF
ON
during run
OFF
during frequency
output
Figure 5.59 Timing Diagram During Frequency Output
Parameter Name
Parameter Name
Control.
Parameter Name
Control.
Description
Drive is producing a frequency output
ON
ON
Setting Range
0: 0.1 kWH units
1: 1 kWH units
2: 10 kWH units
3: 100 kWH units
4: 1000 kWH units
Description
REMOTE
LOCAL
Setting Range
0 to 100
0.0 to 25.5
Setting Range
0 to 100
0.0 to 25.5
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Default
Page
0
Default
Page
0%
1.0 s
Default
Page
100%
1.0 s