YASKAWA V1000 Series Technical Manual page 296

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

B.2 Parameter Table
No.
Name
b1-03
Stopping Method Selection
b1-04
Reverse Operation Selection
b1-07
Local/Remote Run Selection
Run Command Selection while in
b1-08
Programming Mode
b1-14
Phase Order Selection
b1-15
Frequency Reference 2
b1-16
Run Command Source 2
b1-17
Run Command at Power Up
b2-01
DC Injection Braking Start Frequency
b2-02
DC Injection Braking Current
DC Injection Braking Time/DC
b2-03
Excitation Time at Start
b2-04
DC Injection Braking Time at Stop
Magnetic Flux Compensation
b2-08
Capacity
b2-12
Short Circuit Brake Time at Start
b2-13
Short Circuit Brake Time at Stop
b3-01
Speed Search Selection
b3-02
Speed Search Deactivation Current
b3-03
Speed Search Deceleration Time
b3-05
Speed Search Delay Time
b3-06
Output Current 1 during Speed Search
Speed Search Detection Compensation
b3-10
Gain
b3-14
Bi-Directional Speed Search Selection
b3-17
Speed Search Restart Current Level
b3-18
Speed Search Restart Detection Time Sets the time in seconds for speed search restart to be detected.
b3-19
Number of Speed Search Restarts
b3-24
Speed Search Method Selection
b3-25
Speed Search Retry Interval Time
296
Description
Selects the stopping method when the run command is removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection Braking to Stop
3: Coast with Timer
(A new run command is ignored if received before the timer expires)
Permits or prohibits reverse operation.
0: Reverse enabled.
1: Reverse disabled.
Determines the operation when the Run command source is switched from
LOCAL to REMOTE or between Run source 1 and 2 while an external Run
command is active at the new source.
0: External Run command has to be cycled at the new source to be activated.
1: External Run command at new source is accepted immediately.
0: Run command accepted only in the operation menu.
1: Run command accepted in all menus.
2: Prohibit entering programming mode during Run
Sets the phase order for drive output terminals U/T1, V/T2 and W/T3.
0: Standard
1: Switch phase order
Selects the frequency reference input source.0: Operator - Digital preset speed
d1-01 to d1-17.
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse Input (Terminal RP)
Selects the run command input source.
0: Operator - RUN and STOP keys on the digital operator.
1: Digital input terminals S1 to S7
2: MEMOBUS/Modbus communications
3: Option PCB
Determines the operation when a Run command is active at power up of the drive.
0: Run command not issued, needs to be cycled
1: Run command issued, motor operation start
b2: DC Injection Braking
Use b2 parameters to configure DC Injection Braking operation
Sets the frequency at which DC Injection Braking starts when Ramp to Stop
(b1-03 = 0) is selected. If b2-01< E1-09, DC Injection Braking starts at E1-09.
Sets the DC Injection Braking current as a percentage of the drive rated current.
Sets DC Injection Braking time at start. Disabled when set to 0.00 seconds.
Sets DC Injection Braking time at stop.
When b1-03 = 2, actual DC Injection time is calculated as follows:
(b2-04) x 10 x (Output Freq) / (E1-04).
When b1-03 = 0, this parameter sets the amount of DC Injection time applied to
the motor at the end of the decel ramp or High Slip Braking.
Disabled when set to 0.00.
Sets the magnetic flux compensation as a percentage of the no-load current value
(E2-03).
Sets the time for Short-Circuit Brake operation at start. Disabled when set to 0.00.
<32>
Sets Short-Circuit Brake operation time at stop. Used to stop a motor rotating due
to inertia. Disabled when set to 0.00 seconds.
<32>
b3: Speed Search
Use B3 parameters to configure Speed Search function operation.
Enables/disables speed search function at start.0: Disabled - Speed Search is not
automatically performed at start.
1: Enabled - Speed Search is automatically performed at start.
Sets the current level at which the speed is assumed to be detected and Speed
Search is ended. Set in percent of the drive rated current.
Sets the time constant used to reduce the output frequency during speed search.
Related to a change from max. output frequency to 0.
Delays the speed search operation after a momentary power loss to allow time
for an external output contactor to close.
Sets the current injected to the motor at the beginning of Estimation type Speed
Search. Set as a factor to the motor rated current.
Sets the gain which is applied to the speed detected by Speed Estimation Speed
Search before the motor is reaccelerated. Increase this setting if OV occurs when
performing speed search.
Selects if Speed Search detects the motor rotation direction during speed search.
0: Disabled–Frequency reference direction used
1: Enabled–Detected direction used
Sets the speed search restart current level in percentage of the drive rated current.
Sets the number of restarts possible for speed search restart operations.
Sets the Speed Search detection mode.
0: Current Detection Type
1: Speed Estimation Type
Sets the wait time before Speed Search restarts.
Range
DC Injection Braking at Stop cannot be selected when using
Open Loop Vector for PM motors.
0.0 to 10.0
0 to 75
0.00 to 10.00
0.00 to 10.00
0 to 1000
0.00 to 25.50
0.00 to 25.50
0 to 200
0.1 to 10.0
0.0 to 100
0.0 to 2.0
1.00 to 1.20
0 to 200
0.00 to 1.00
0 to 10
0 to 30.0
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Control
Mode
Addr.
Def.
V/f OL V PM
0 to 3
0
S
S
S
0, 1
0
A
A
A
0, 1
0
A
A
A
0 to 2
0
A
A
A
0, 1
0
A
A
A
0 to 4
0
A
A
A
0 to 3
0
A
A
A
0, 1
0
A
A
A
0.5 Hz
A
A
A
50%
A
A
0.00 s
A
A
<1>
0.50 s
A
A
0%
A
0.00 s
A
0.50 s
A
0 to 1
0
A
A
A
120
<2>
A
A
2.0 s
A
A
0.2 s
A
A
A
A
A
<12>
1.05
A
A
0, 1
0
A
A
150%
A
A
0.10 s
A
A
3
A
A
0, 1
0
A
A
0.5 s
A
A
A
Pg.
Hex
182
78
183
186
187
1C3
1C4
1C5
1C6
189
18A
18B
18C
190
1BA
1BB
191
192
193
195
196
19A
19E
1F0
1F1
1F2
1C0
1C8