YASKAWA V1000 Series Technical Manual page 165

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

Setting Up the Jog Function
This example shows how terminal S7 (H1-07) activates the Forward Jog function.
1.
Turn on the power to the drive.
2.
Press
until the parameter setting screen is displayed.
3.
Press
to enter the list of parameters.
4.
Press
to enter the list of parameters.
5.
Use the
and
Function Selection). Note: selecting any parameter between H1-01 to H1-07 will produce the same result.
6.
Press
to display the setting value for H1-07.
7.
Use the
and
8.
Press
to save the settings.
1.
Turn on the power to the drive, making sure the drive is set to REMOTE
Close terminal S7 and run the drive at 6.00 Hz. Note: when the Jog reference is input, there is no need to enter a run
2.
command.
3.
Open terminal S7 to stop the drive.
Setting 14: Fault Reset
Whenever the drive detects a fault condition, the fault output contact will close and the drive's output will shut off. The motor then coasts to stop (specific
stopping methods can be selected for some faults such as L1-04 for motor overheat). Once the run command is removed, the fault can be cleared by either
the RESET key on the digital operator or by closing a digital input configured as a Fault Reset (H1-oo = 14).
Note: Fault reset commands are ignored as long as the Run command is present. To reset a fault, first remove the Run command.
Setting 15: Fast Stop, N.O.
Setting 17: Fast Stop, N.C.
The Fast Stop function operates much like an emergency stop input to the drive. While in the run mode, if a Fast Stop is input to the drive, the drive will
decelerate to a stop with the deceleration time determined by C1-09 (Fast Stop Time).
• To trigger the Fast Stop function with a N.O. switch, set 15
• To trigger the Fast Stop function with a N.C. switch, set 16
The drive will not run from either the terminals or the digital operator while the Fast Stop is being input. To restart the drive, the Fast Stop input must be
removed and the Run command must be cycled.
No.
Parameter Name
C1-09
Fast Stop Time
The Fast Stop feature is also available as one of the stopping methods for when a fault is detected.Therefore, be sure to set an acceptable deceleration time
in parameter C1-09 when using the Fast Stop feature.
Note: The setting range of C1-09 is dependent on C1-10 Accel/Decel Time Setting Unit.
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Output
Frequency
Jog Reference
(FJ0G)
Figure 5.41 Jog Sequence
Procedure
keys to scroll to parameter H1-07 (Multi-Function Digital Input Terminal S7
keys to set 12 (the setting value for Forward Jog.) Note: set 13 for Reverse Jog.
Procedure
6.0 Hz
ON
Setting Range
0.0 to 6000.0
5.7 H: Terminal Functions
Display/Result
Display/Result
F00.00
Motor
Forward
Default
10.0 s
5
Page
165