2 Methods for Connecting and Communicating with External Devices
2-4-7

IO Data Communication Settings

This section describes how to set data links for PROFINET.
The communication areas in the PLC used for IO data communications with the Sensor Controller are
set by assigning the I/O memory address with an engineering tool such as CX Configurator FDT.
When an OMRON controller is connected and communicate via PROFINET, use CX Configurator FDT
to assign the I/O memory address.
Here, describes how to set the I/O memory address using CX Configurator FDT. For details, refer to
CJ series PROFINET I/O Controller Unit Operation Manual for NJ series CPU Unit(W511-E2-01).
Precautions for Correct Use
When connecting to a CPU Unit of NJ series or CJ series, install the GSD file that defines the
IO data CR connection information for the Sensor Controller to a tool (e.g. CX Configurator
FDT). Download the GSD file from OMRON's website.
IO Data CR Connection Settings for the Sensor Controller
Each communication area in the PLC is set as IO data CR connections as shown below
Settings for the Sensor Controller (Module Settings)
1
Add an IO device (FZ/FH-XXXX/FHV7) to the IO controller of the CX Configurator FDT.
2
Select Configuration -> Modules in the IO device (FZ/FH-XXXX/FHV7).
3
Add Input Data to the slot 1 and Output Data to the slot 2.
4
Add a Sub-module to the Sub-slot in Slot 1 and set the data format. Likewise, do slot 2.
The types of the data format must be the same as the Output data size set at PROFINET of
the Sensor Controller.
*1:
For Multi-line Random-trigger Mode, add the sub-modules corresponding to the number of lines to
the Input Data and Output Data respectively.
2 - 276
FH/FHV Series Vision System User's manual for Communication Settings (Z342-E1)