FC 300 Design Guide
Control Word according to PROFIdrive
"
Profile (CTW)
The Control word is used to send commands
from a master (e.g. a PC) to a slave.
Explanation of the Control Bits
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Bit 00, OFF 1/ON 1:
Normal ramp stop uses the ramp times of the actual selected ramp. Bit 00 = "0": Stops and activates
the output relay 1 or 2, if the output frequency is 0 Hz and if Relay 123 is selected in par. 5-40. Bit
00 = "1": The adjustable frequency drive starts if the other start conditions are met.
Bit 01, OFF 2/ON 2
Bit 01 = "0": Coasting stop and activation of the output relay 1 or 2 occurs if the output
frequency is 0 Hz and if Relay 123 is selected in par. 5-40. Bit 01 = "1": The adjustable
frequency drive starts if the other start conditions are met.
Bit 02, OFF 3/ON 3
A quick stop uses the ramp time of par. 2-12. Bit 02 = "0": A quick stop and activation of the output
relay 1 or 2 occurs if the output frequency is 0 Hz and if Relay 123 is selected in par. 5-40. Bit 02 =
"1": The adjustable frequency drive starts if the other start conditions are met.
Bit 03, Coasting/No coasting
Bit 03 = "0": Leads to a stop. Bit 03 = "1": The adjustable frequency drive starts
if the other start conditions are met.
default setting
( )
display text
*
248
How to Program
Bit value = 0
OFF 1
OFF 2
OFF 3
Coasting
Quick stop
Hold frequency output.
Ramp stop
No function
Jog 1 OFF
Jog 2 OFF
Data invalid
No function
No function
Selection set-up 1 (lsb)
Selection set-up 2 (lsb)
No function
[ ]
value for use in communication via serial communication port
MG.33.B3.22 - VLT is a registered Danfoss trademark
Master => slave
1
2
3
CTW
MRV
PCD
PCD read/write
Bit value = 1
ON 1
ON 2
ON 3
No coasting
Ramp
Use ramp
Start
Reset
Jog 1 ON
Jog 2 ON
Data valid
Slow down
Catch up
Selection set-up 1 (lsb)
Selection set-up 2 (lsb)
Reverse
.....
10
.....