FC 300 Design Guide
Function:
When set to Off [0], the Digital Potentiometer
reference will be reset to 0% after power-up.
If set to On [1], the last Digital Potentiometer
reference will be restored at power-up.
3-93 Maximum Limit
Range:
0 - 200 %
Function:
Set the maximum value that the Digital
Potentiometer reference is allowed to attain. This is
advisable if the Digital Potentiometer is only meant
for fine tuning of the resulting reference.
3-94 Minimum Limit
Range:
-200 - 200 %
Function:
Set the minimum value that the Digital
Potentiometer reference is allowed to attain. This is
advisable if the Digital Potentiometer is only meant
for fine tuning of the resulting reference.
3-95 Ramp Delay
Range:
0.000 - 3600.00 s
Function:
Adjust the delay before the adjustable frequency
drive starts to ramp the reference. With a delay
of 0 ms, the reference starts to ramp as soon as
the INCREASE / DECREASE goes high.
default setting
( )
display text
*
162
How to Program
*
100%
*
-100%
*
1.000s
[ ]
value for use in communication via serial communication port