FC 300 Design Guide

Additional Text

"
With this feature, it is possible to read additional
text if bit 10, Additional text available, is
true in Basic characteristics.
To read out additional text, the parameter command
(PKE) must be set to F hex, see Databytes.
The index field is used for pointing out which
element to read. Valid indexes are in the range
of 1 through 254. The index must be calculated
according to the following equation:
Index = Parameter value + 1 (see table below).
Example:
In this example, the Master reads additional text in par. 0-01, Language. The telegram is set up to read
data value [0] (English). You must send the following telegram to the adjustable frequency drive:
STX
LGE
02
0E
STX =
02 Start byte
LGE =
0E Length of the remaining telegram
ADR =
Send the VLT adjustable frequency drive on Address 1, Danfoss format
PKE =
F001; F in the PKE field indicates a Read text and 01 indicates par. 0-01, Language.
IND =
0001; 1 indicates that text to parameter value [0] is required
The response from the adjustable frequency drive is:
STX
LGE
02
11
PKE =
F001; F is the response for Text transfer and 01 indicates par. 0-01, Language.
IND =
0001; 1 indicates that index [1] is sent
PVA =
45 4E 47 4C 49 53 48
E N G L I S H
The parameter value channel is now set up to a visible string, which returns an ASCII
character for each letter in the index name.
*
default setting
( )
How to Program
ADR
PKE
IND
01
F0 01
00 01
ADR
PKE
IND
01
F0 01
00 01
display text
[ ]
value for use in communication via serial communication port
MG.33.B3.22 - VLT is a registered Danfoss trademark
Value
Index
0
1
1
2
2
3
3
4
4
5
5
6
PWE
PWE
PCD1
HIGH
LOW
00 00
00 00
XX XX
PVA
PCD1
454E 474C 4953 48
XX XX
Text
English
Deutsch
Français
Dansk
Espanol
Italiano
PCD2
BCC
XX XX
XX
PCD2
BCC
XX XX
XX
261