Danfoss VLT AutomationDrive FC 300 Design Manual page 188

Hide thumbs Also See for VLT AutomationDrive FC 300:
Table of Contents

Advertisement

FC 300 Design Guide
16-80 Fieldbus CTW 1
16-82 Fieldbus REF 1
16-84 Comm Option STW
16-85 FC Port CTW 1
16-90 Alarm Word
16-91 Alarm Word 2
16-92 Warning Word
16-93 Warning Word 2
16-94 Extended Status Word
16-95 Extended Status Word 2
Function:
Contains a list of signals that can be entered
in par. 9-15 and 9-16. Furthermore, it
automatically sets the parameters to meet the
most common requirements.
9-27 Parameter Edit
Option:
Disabled
*
Enabled
Function:
You can edit parameters via Profibus, the standard
RS-485 Interface, or the LCP. Disable editing
via Profibus with this parameter.
9-28 Process Control
Option:
Disable
*
Enable cyclic master
Function:
Process control (setting of Control Word, speed
reference, and process data) is possible via either
Profibus or the standard RS-485 Interface but not
both at the same time. Local control is always
possible via the LCP. Control via process control is
possible with either terminals or bus depending
on the setting of par. 8-50 to 8-56.
- Disable: Disables process control via Profibus, and
enables process control via standard RS-485.
- Enable cyclic master: Enables process control
via Profibus Master Class 1, and disables process
control via standard RS-485 bus or Master class 2.
9-44 Fault Message Counter
Range:
0 - 65535 N/A
default setting
( )
display text
*
188
How to Program
Indicates the number of alarms presently
stored in par. 9-47. The buffer capacity is
maximum eight error events.
This parameter contains the alarm word from
all alarm messages occurred.
The buffer capacity is maximum eight error events.
This parameter contains the alarm number
[0]
(e.g. 2 for live zero error, 4 for line phase
[1]
loss) that occurs for an event.
The buffer capacity is maximum eight error events.
This parameter contains the number of events
[0]
presently stored since last reset/power-up.
[1]
Par. 9-52 is incremented for every event
(by AOC or Profibus option).
*
0N/A
[ ]
value for use in communication via serial communication port
MG.33.B3.22 - VLT is a registered Danfoss trademark
Function:
9-45 Fault Code
Range:
0 - 0 N/A
Function:
9-47 Fault Number
Range:
0 - 0 N/A
Function:
9-52 Fault Situation Counter
Range:
0 - 1000 N/A
Function:
*
0 N/A
*
0 N/A
*
0N/A