FC 300 Design Guide
Brake ready, no fault
ready for operation and there are no faults.
Brake fault (IGBT)
"1" when the brake IGBT is short-circuited. Use
this function to protect the adjustable frequency
drive if there is a fault on the brake modules.
Use the output/relay to cut out the line voltage
from the adjustable frequency drive.
Relay 123
[31]: If Fieldbus profile [0]
is selected in par. 5-12, the relay is
activate. If OFF1, OFF2 or OFF3 (bit in
the control word) is Logic '1'.
Mech. brake control
control of an external mechanical brake, see
description in the section Control of Mechanical
Brake, and par. group 2-2*
Safe stop active
[33]: Indicates that the safe
stop on terminal 37 has been activated.
MCO controlled [51]
Comparator 0
[60]: See par. group 13-1*. If
Comparator 0 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Comparator 1
[61]: See par. group 13-1*. If
Comparator 1 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Comparator 2
[62]: See par. group 13-1*. If
Comparator 2 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Comparator 3
[63]: See par. group 13-1*. If
Comparator 3 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Logic Rule 0
[70]: See par. group 13-4*. If
Logic Rule 0 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Logic Rule 1
[71]: See par. group 13-4*. If
Logic Rule 1 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Logic Rule 2
[72]: See par. group 13-4*. If
Logic Rule 2 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Logic Rule 3
[73]: See par. group 13-4*. If
Logic Rule 3 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
SL digital output A
SL Controller Action. The input will go high
whenever the Smart Logic Action [38] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [32]
"Set dig. out. A low" is executed.
default setting
( )
display text
*
170
How to Program
[29]: The brake is
[30]: The output is Logic
[32]: Enables
[80]: See par. 13-52
[ ]
value for use in communication via serial communication port
MG.33.B3.22 - VLT is a registered Danfoss trademark
SL digital output B
SL Controller Action. The input will go high
whenever the Smart Logic Action [39] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [33]
"Set dig. out. A low" is executed.
SL digital output C
SL Controller Action. The input will go high
whenever the Smart Logic Action [40] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [34]
"Set dig. out. A low" is executed.
SL digital output D
SL Controller Action. The input will go high
whenever the Smart Logic Action [41] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [35]
"Set dig. out. A low" is executed.
SL digital output E
SL Controller Action. The input will go high
whenever the Smart Logic Action [42] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [36]
"Set dig. out. A low" is executed.
SL digital output F
SL Controller Action. The input will go high
whenever the Smart Logic Action [43] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [37]
"Set dig. out. A low" is executed.
Local ref. active
[120]: The output will
be high if par. 3-13 Reference Site = [2]
"Local" or when par. 3-13 Reference Site
= [0] "Linked to Hand / Auto" at the same
time the LCP is in Hand on mode.
Remote ref. active
be high if par. 3-13 Reference Site = [1]
"Remote" or when par. 3-13 Reference Site
= [0] Linked to Hand / Auto at the same
time the LCP is in Auto on mode.
No alarm
[122]: The output goes high
when no alarm is present.
Start cmd. active
[123]: The output
goes high whenever there is an active Start
command (i.e. via digital input bus connection
or [Hand on] or [Auto on], and no Stop
or Start command is active.
Running reverse
[124]: The output is high
whenever the drive is running counterclockwise
[81]: See par. 13-52
[82]: See par. 13-52
[83]: See par. 13-52
[84]: See par. 13-52
[85]: See par. 13-52
[121]: The output will