FC 300 Design Guide
Brake ready, no fault
•
ready for operation and there are no faults.
•
Brake fault (IGBT)
"1" when the brake IGBT is short-circuited. Use
this function to protect the adjustable frequency
drive if there is a fault on the brake modules.
Use the output/relay to cut out the line voltage
from the adjustable frequency drive.
Relay 123
[31]: If Fieldbus profile [0]
•
is selected in par. 5-12, the relay is
activate. If OFF1, OFF2 or OFF3 (bit in
the control word) is Logic '1'.
Mech. brake control
•
control of an external mechanical brake, see
description in the section Control of Mechanical
Brake, and par. group 2-2*
Safe stop active
[33]: Indicates that the safe
•
stop on terminal 37 has been activated.
•
MCO controlled [51]
Comparator 0
[60]: See par. group 13-1*. If
•
Comparator 0 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
•
Comparator 1
[61]: See par. group 13-1*. If
Comparator 1 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Comparator 2
[62]: See par. group 13-1*. If
•
Comparator 2 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Comparator 3
[63]: See par. group 13-1*. If
•
Comparator 3 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Logic Rule 0
[70]: See par. group 13-4*. If
•
Logic Rule 0 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Logic Rule 1
[71]: See par. group 13-4*. If
•
Logic Rule 1 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Logic Rule 2
[72]: See par. group 13-4*. If
•
Logic Rule 2 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Logic Rule 3
[73]: See par. group 13-4*. If
•
Logic Rule 3 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
•
SL digital output A
SL Controller Action. The input will go high
whenever the Smart Logic Action [38] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [32]
"Set dig. out. A low" is executed.
default setting
( )
display text
*
170
How to Program
[29]: The brake is
[30]: The output is Logic
[32]: Enables
[80]: See par. 13-52
[ ]
value for use in communication via serial communication port
MG.33.B3.22 - VLT is a registered Danfoss trademark
SL digital output B
•
SL Controller Action. The input will go high
whenever the Smart Logic Action [39] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [33]
"Set dig. out. A low" is executed.
•
SL digital output C
SL Controller Action. The input will go high
whenever the Smart Logic Action [40] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [34]
"Set dig. out. A low" is executed.
SL digital output D
•
SL Controller Action. The input will go high
whenever the Smart Logic Action [41] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [35]
"Set dig. out. A low" is executed.
•
SL digital output E
SL Controller Action. The input will go high
whenever the Smart Logic Action [42] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [36]
"Set dig. out. A low" is executed.
SL digital output F
•
SL Controller Action. The input will go high
whenever the Smart Logic Action [43] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [37]
"Set dig. out. A low" is executed.
Local ref. active
[120]: The output will
•
be high if par. 3-13 Reference Site = [2]
"Local" or when par. 3-13 Reference Site
= [0] "Linked to Hand / Auto" at the same
time the LCP is in Hand on mode.
•
Remote ref. active
be high if par. 3-13 Reference Site = [1]
"Remote" or when par. 3-13 Reference Site
= [0] Linked to Hand / Auto at the same
time the LCP is in Auto on mode.
No alarm
[122]: The output goes high
•
when no alarm is present.
Start cmd. active
[123]: The output
•
goes high whenever there is an active Start
command (i.e. via digital input bus connection
or [Hand on] or [Auto on], and no Stop
or Start command is active.
•
Running reverse
[124]: The output is high
whenever the drive is running counterclockwise
[81]: See par. 13-52
[82]: See par. 13-52
[83]: See par. 13-52
[84]: See par. 13-52
[85]: See par. 13-52
[121]: The output will