Emc Test Results (Emission, Immunity) - Danfoss VLT AutomationDrive FC 300 Design Manual

Hide thumbs Also See for VLT AutomationDrive FC 300:
Table of Contents

Advertisement

EMC Test Results (Emission, Immunity)

The following test results have been obtained using a system with an adjustable frequency drive (with options if relevant), a shielded control cable,
a control box with potentiometer, as well as a motor and motor cable.
FC 301/FC 302
200-240 V
Environment
380-500 V
Basic standard
Setup
Motor cable
FC 301/FC 302 A2
16 ft (5 m) shielded/ar-
0-5 HP (0-3.7 kW) 200-240 V
mored
0-10 HP (0-7.5 kW) 380-500 V
33 ft (10 m)
shielded/armored
FC 301 with integrated filter
131 ft (40 m)
0-5 HP (0-3.7 kW) 200-240 V
shielded/armored
0-10 HP (0-7.5 kW) 380-500 V
492 ft (150 m)
non-shielded/unarmored
131 ft (40 m)
shielded/armored
FC 302 with integrated filter
492 (150 m)
0-5 HP (0-3.7 kW) 200-240 V
shielded/armored
0-10 HP (0-7.5 kW) 380-500 V
984 ft (300 m)
non-shielded/unarmored
Conducted emission
Industrial environment
Housing, trades
EN 55011 Class
EN 55011 Class
A2
A1
Yes
No
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Yes
No
No
Radiated emission
Industrial
Housing, trades
and light
environment
and light
industries
industries
EN 55011
EN 55011 Class
EN 55011 Class B
Class B
A1
No
No
Yes
Yes
No
Yes
No
No
Yes
Yes
No
Yes
No
No
No
No
No
No
No
No
No

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents