Danfoss VLT AutomationDrive FC 300 Design Manual page 206

Hide thumbs Also See for VLT AutomationDrive FC 300:
Table of Contents

Advertisement

FC 300 Design Guide
14-2* Trip Reset
"
14-20 Reset Mode
Option:
*
Manual reset
Automatic reset x 1
Automatic reset x 2
Automatic reset x 3
Automatic reset x 4
Automatic reset x 5
Automatic reset x 6
Automatic reset x 7
Automatic reset x 8
Automatic reset x 9
Automatic reset x 10
Automatic reset x 15
Automatic reset x 20
Infinite Automatic Reset
Function:
Selects the reset function after tripping.
Upon reset, It is also possible to restart the
adjustable frequency drive.
Selecting Manual reset [0], allows a reset via
[RESET] or via the digital inputs. If it is desired
the adjustable frequency drive performs an
automatic reset (1-10 times) after tripping,
select data value [1]-[10].
NOTE
If the number of AUTOMATIC RESETs is
reached within 10 minutes, the adjustable
frequency drive enters Manual reset [0]
mode. When a Manual reset is performed, the
parameter setting is back in force. If the number
of AUTOMATIC RESETs is not reached within 10
minutes, the internal AUTOMATIC RESET counter
is reset. Also, if a Manual reset is performed, the
internal AUTOMATIC RESET counter is reset.
The motor may start without warning.
14-21 Automatic Restart Time
Range:
0 - 600 s
Function:
Sets the time from tripping until the automatic
reset function begins. Select automatic reset in
par. 14-20 to program the parameter.
default setting
( )
display text
*
206
How to Program
Set the desired time.
[0]
*
[1]
[2]
[3]
[4]
[5]
Used for two different tests in addition to its normal
[6]
function. It is also possible to initialize all parameters
[7]
(except par. 15-03, 15-04 and 15-05). This function
[8]
is not active until you turn off mains supply to the
[9]
adjustable frequency drive and then turn it on again.
[10]
Select Normal operation [0] for normal operation
[11]
with the motor in the selected application.
[12]
Select Control card test [1] to test the analog
[13]
and digital inputs and outputs and the +10
V control voltage. The test requires a test
connector with internal connections.
Use the following procedure for the control card test:
1.
2.
3.
4.
5.
6.
7.
8.
Carry out a power cycle to start up in Normal
operation after a control card test.
If the test is OK:
LCP readout:
Control Card OK.
Cut off mains supply and remove the test plug. The
green LED on the Control Card is turned on.
If the test fails:
LCP readout:
*
10s
Control Card I/O failure. Replace the unit or Control
card. The red LED on the Control Card is turned on.
Test plugs (connect the following terminals to each
other): 18 - 27 - 32; 19 - 29 - 33; 42 - 53 - 54
[ ]
value for use in communication via serial communication port
MG.33.B3.22 - VLT is a registered Danfoss trademark
14-22 Operation Mode
Option:
Normal operation
Control card test
Initialization
Function:
Select Control card test.
Cut off the mains supply and wait for the
light in the display to go out.
Set switches S201 (A53) and S202
(A54) = "ON" / I.
Insert the test plug (see below).
Connect to mains.
Carry out various tests.
The result is written on the LCP and the
drive moves into an infinite loop.
Par. 14-22 is automatically set to
Normal operation.
[0]