FC 300 Design Guide
NOTE
An active HAND-OFF-AUTO signal via the digital inputs has higher priority than
the control keys [Hand on] – [Auto on].
[Reset]
is used for resetting the adjustable frequency drive after an alarm (trip). It can be
selected as Enable [1] or Disable [0] via par. 0-43 Reset Key on LCP.
Arrow
keys are used for maneuvering between commands and within parameters.
The parameter shortcut
The parameter shortcut allows direct access to any parameter.
Quick Transfer of Parameter Settings
"
Once the setup of a drive is complete, it is
recommended that the data is stored in the LCP
or on a PC via MCT 10 Setup Software Tool.
Data storage in LCP:
Go to par. 0-50 LCP copy
1.
Press the [OK] key
2.
3.
Select "All to LCP"
Press the [OK] key
4.
All parameter settings are now stored in the LCP indicated by the progress bar.
When 100% is reached, press [OK].
NOTE
Stop the unit before performing this operation.
It is now possible to connect the LCP to another adjustable frequency drive and copy the
parameter settings to this adjustable frequency drive as well.
Data transfer from LCP to drive:
1.
Go to par. 0-50 LCP copy
Press the [OK] key
2.
Select "All from LCP"
3.
Press the [OK] key
4.
The parameter settings stored in the LCP are now transferred to the drive indicated by
the progress bar. When 100% is reached, press [OK].
NOTE
Stop the unit before performing this operation.
How to Program
can be carried out by holding down the [Main Menu] key for 3 seconds.
MG.33.B3.22 - VLT is a registered Danfoss trademark
121