Parameters: Devicenet Can Fieldbus - Danfoss VLT AutomationDrive FC 300 Design Manual

Hide thumbs Also See for VLT AutomationDrive FC 300:
Table of Contents

Advertisement

FC 300 Design Guide
Parameters: DeviceNet
"
CAN Fieldbus
10-0* Common Settings
"
10-00 CAN Protocol
Option:
*
DeviceNet
Function:
Selection of CAN protocol.
10-01 Baud Rate Select
Option:
*
125 Kbps
250 Kbps
500 Kbps
Function:
Selection of the DeviceNet transmission speed. The
selection must correspond to the transmission speed
of the master and the other DeviceNet nodes.
10-02 MAC ID
Option:
0 - 127 N/A
Function:
Selection of station address. Every station
connected to the same DeviceNet network must
have an unambiguous address.
10-05 Readout Transmit Error Counter
Range:
0 - 255
Function:
A readout of the Transmit Error Counter of the
CAN controller since the last power-up.
10-06 Readout Receive Error Counter
Range:
0 - 255
Function:
Displays the Receive Error Counter of the CAN
controller since the last power-up.
10-07 Readout Bus Off Counter
Range:
0 - 1000
default setting
( )
display text
*
192
How to Program
Displays the number of Bus Off events
since the last power-up.
10-1* DeviceNet
"
[1]
Permits selection of 6 different Instances for data
[20]
transmission. Instances 100/150 and 101/151 are
[21]
Danfoss-specific. Instance 20/70, 21/71, 22/72,
[22]
and 23/73 are ODVA-specific AC Drive profiles.
A change to this parameter is not executed
until the next power-up.
*
63 N/A
*
0
*
0
Used for the pre-defined I/O assembly Instances.
Only 2 elements [1,2] of this array are used. All
elements are set to 0 as default.
*
0
[ ]
value for use in communication via serial communication port
MG.33.B3.22 - VLT is a registered Danfoss trademark
Function:
10-10 Process Data Type Selection
Option:
Instance 100/150
Instance 101/151
Instance 20/70
Instance 21/71
Function:
10-11 Process Data Config Write
Option:
None
Minimum reference par. 3-02
Maximum reference par. 3-03
Catch up/slow down value par. 3-12
Ramp 1 ramp up time par. 3-41
Ramp 1 ramp down time par. 3-42
Ramp 2 ramp up time par. 3-51
Ramp 2 ramp down time par. 3-52
Jog ramp time par. 3-80
Quick stop ramp time par. 3-81
Motor speed low limit par. 4-11
Motor speed high limit par. 4-13
Torque limit motor mode par. 4-16
Torque limit generator mode par. 4-17
Bus Jog 1 Speed par. 8-90
Bus Jog 2 Speed par. 8-91
Fieldbus CTW 1 par. 16-80
Fieldbus REF 1 par. 16-82
Function:
10-12 Process Data Config Read
Option:
None
[0]
[1]
[2]
[3]
[0]
[RPM]
[RPM]
[10]