5 Calibration
5.3 Updating revolution counters
Continued
2
3
Continues on next page
406
Action
All mechanical units connected to the system are shown with their calibration status.
Tap the mechanical unit in question.
xx1500000943
This step is valid for RobotWare 6.02 and later.
Calibration method used at factory for each axis is shown, as well as calibration
method used during last field calibration.
Tap Manual Method (Advanced).
xx1500000944
© Copyright 2007 - 2018 ABB. All rights reserved.
Product manual - IRB 7600
3HAC022033-001 Revision: V