Technical Data; Motor Requirements; Temperature, Humidity And Cooling Method; Storage - Emerson E300 Series Design Manual

Advanced elevator drive / dedicated elevator variable speed ac drive for induction and permanent magnet motors
Hide thumbs Also See for E300 Series:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
12

Technical Data

12.1

Motor requirements

No. of phases: 3
Maximum voltage:
200 V drive: 240 V
400 V drive: 480 V
575 V drive: 575 V
690 V drive: 690 V
12.2

Temperature, humidity and cooling method

Ambient temperature operating range:
- 20 °C to 50 °C (- 4 °F to 122 °F).
Output current derating must be applied at ambient temperatures >40 °C (104 °F).
Cooling method: Forced convection
Maximum humidity: 95 % non-condensing at 40 °C (104 °F)
12.3

Storage

-40 °C (-40 °F) to +50 °C (122 °F) for long term storage, or to +70 °C (158 °F) for short term storage.
Storage time is 2 years.
Electrolytic capacitors in any electronic product have a storage period after which they require reforming or replacing.
The DC bus capacitors have a storage period of 10 years.
The low voltage capacitors on the control supplies typically have a storage period of 2 years and are thus the limiting factor.
Low voltage capacitors cannot be reformed due to their location in the circuit and thus may require replacing if the drive is stored for a period of 2
years or greater without power being applied.
It is therefore recommended that drives are powered up for a minimum of 1 hour after every 2 years of storage.
This process allows the drive to be stored for a further 2 years.
12.4

Altitude

Altitude range: 0 to 3,000 m (9,900 ft), subject to the following conditions:
1,000 m to 3,000 m (3,300 ft to 9,900 ft) above sea level: de-rate the maximum output current from the specified figure by 1% per 100 m (330 ft)
above 1,000 m (3,300 ft)
For example at 3,000 m (9,900 ft) the output current of the drive would have to be de-rated by 20 %.
12.5

IP / UL Rating

The drive is rated to IP20 pollution degree 2 (dry, non-conductive contamination only) (NEMA 1). However, it is possible to configure the drive to
achieve IP65 rating (sizes 3 to 7) (NEMA 12) at the rear of the heatsink for through-panel mounting (some current derating is required).
In order to achieve the high IP rating at the rear of the heatsink with drive sizes 3,4 and 5 it is necessary to seal a heatsink vent by installing the high
IP insert.
The IP rating of a product is a measure of protection against ingress and contact to foreign bodies and water. It is stated as IP XX, where the two
digits (XX) indicate the degree of protection provided as shown in Table 12-1.
Table 12-1 IP Rating degrees of protection
Protection against contact and ingress of foreign bodies
0
No protection
Protection against large foreign bodies φ > 50 mm (large area
1
contact with the hand)
Protection against medium size foreign bodies φ > 12 mm
2
(finger)
Protection against small foreign bodies φ > 2.5 mm (tools, wires)
3
Protection against granular foreign bodies φ > 1mm (tools,
4
wires)
Protection against dust deposit, complete protection against
5
accidental contact.
Protection against dust ingress, complete protection against
6
accidental contact.
7
8
484
Electrical
Getting
User Menu A Commissioning
installation
started
First digit
Advanced
Diagnostics Optimization CT MODBUS RTU
Parameters
Second digit
Protection against ingress of water
0
No protection
1
Protection against vertically falling drops of water
2
Protection against spraywater (up to 15 ° from the vertical)
Protection against spraywater (up to 60 ° from the vertical)
3
4
Protection against splashwater (from all directions)
Protection against heavy splash water (from all directions, at high
5
pressure)
6
Protection against deckwater (e.g. in heavy seas)
7
Protection against immersion
8
Protection against submersion
Technical Data