the logic for Digital I/O1-6 to negative logic, so that the state parameter is 0 if the digital I/O is high or 1 if the digital I/O is low. The state parameter
represents the digital I/O state whether it is an input or an output.
Digital Input 11 (Keypad Run Button), Digital Input 12 (Keypad Auxiliary Button) and Digital Input 14 (Keypad Stop Button) represent the state of the
Run, Auxiliary and Stop buttons on any keypad fitted to the drive; the input state is determined by ORing the state of the button on each keypad
connected to the drive, if the button is pressed the state parameter is one otherwise it is zero. If a keypad is not fitted the state parameters are zero.
Digital Input 13 (24V Supply Input) is an external 24 V supply input that is monitored and can be used as a 24 V digital input if an external 24 V supply
is not required. The state parameter is low for the voltage range from 0 V to 17 V and high for the voltage range above 18 V. As the input is a power
supply it will consume significant current if the level is taken above 24 V when the drive is running from its internal power supply, or at any voltage
level if this input is the only power supply to the drive.
F04
Mode
Minimum
Default
Type
Display Format
Coding
See T24 Digital I/O 01 State (F03).
F05
Mode
Minimum
Default
Type
Display Format
Coding
See T24 Digital I/O 01 State (F03).
F06
Mode
Minimum
Default
Type
Display Format
Coding
See T24 Digital I/O 01 State (F03).
F07
Mode
Minimum
Default
Type
Display Format
Coding
See T24 Digital I/O 01 State (F03).
F08
Mode
Minimum
Default
Type
Display Format
Coding
See T24 Digital I/O 01 State (F03).
E300 Design Guide
Issue Number: 1
Electrical
Getting
User Menu A Commissioning
installation
started
T25 Digital I/O 02 State
Open-Loop, RFC-A, RFC-S
0
1 Bit Volatile
Standard
RO, ND, NC, PT
T26 Digital I/O 03 State
Open-Loop, RFC-A, RFC-S
0
1 Bit Volatile
Standard
RO, ND, NC, PT
T27 Digital Input 04 State
Open-Loop, RFC-A, RFC-S
0
1 Bit Volatile
Standard
RO, ND, NC, PT
T28 Digital Input 05 State
Open-Loop, RFC-A, RFC-S
0
1 Bit Volatile
Standard
RO, ND, NC, PT
T29 Digital Input 06 State
Open-Loop, RFC-A, RFC-S
0
1 Bit Volatile
Standard
RO, ND, NC, PT
Advanced
Diagnostics Optimization CT MODBUS RTU Technical Data
Parameters
Maximum
1
Units
Update Rate
2 ms write
Decimal Places
0
Maximum
1
Units
Update Rate
2 ms write
Decimal Places
0
Maximum
1
Units
Update Rate
2 ms write
Decimal Places
0
Maximum
1
Units
Update Rate
2 ms write
Decimal Places
0
Maximum
1
Units
Update Rate
2 ms write
Decimal Places
0
269