Emerson E300 Series Design Manual page 248

Advanced elevator drive / dedicated elevator variable speed ac drive for induction and permanent magnet motors
Hide thumbs Also See for E300 Series:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
Apply Frequency (D09), but the motor is not required to stop (i.e. reversing direction without stopping) then Reference On (D10) will be one, and so
the brake is not applied. This prevents the brake from activating and de-activating as the motor passes through zero speed. If the frequency falls
below Brake Control: Brake Apply Frequency (D09) and Reference On (D10) = 0 then the brake will be applied.
D09
Brake Control: Brake Apply Frequency [Open-Loop]
D09
Brake Control: Brake Apply Frequency [RFC-A, RFC-S]
Mode
Open Loop, RFC-A, RFC-S
Minimum
0.0
Open-Loop: 2.0
Default
RFC-A, RFC-S: 5
Type
8 Bit User Save
Display Format
Standard
Coding
RW, BU
Open-Loop
The frequency comparator is used on starting, to detect when the motor frequency has reached a level where the motor can produce the required
amount of torque to ensure that the motor rotates in the demanded direction when the brake is released. Brake Control: Brake Release Frequency
(D08) should be set to a level slightly above the motor slip frequency that is likely to occur under the highest expected load that is applied to the motor
when the brake is released.
The brake apply frequency threshold is used to ensure that the brake is applied before the motor frequency reaches zero and to prevent the motor
rotating (in the reverse direction due to an overhauling load for example) during the brake apply time. If the frequency falls below Brake Control: Brake
Apply Frequency (D09), but the motor is not required to stop (i.e. reversing direction without stopping) then Reference On (D10) will be one, and so
the brake is not applied. This prevents the brake from activating and de-activating as the motor passes through zero speed. If the frequency falls
below Brake Control: Brake Apply Frequency (D09) and Reference On (D10) = 0 then the brake will be applied.
RFC-A, RFC-S
The speed comparator is used on starting, to detect when the motor speed has reached a level where the motor can produce the required amount of
torque to ensure that the motor rotates in the demanded direction when the brake is released. Brake Control: Brake Release Speed (D08) should be
set to a level slightly above the motor slip frequency that is likely to occur under the highest expected load that is applied to the motor when the brake
is released.
The brake apply speed threshold is used to ensure that the brake is applied before the motor speed reaches zero and to prevent the motor rotating (in
the reverse direction due to an overhauling load for example) during the brake apply time. If the speed falls below Brake Control: Brake Apply Speed
(D09), but the motor is not required to stop (i.e. reversing direction without stopping) then Reference On (D10) will be one, and so the brake is not
applied. This prevents the brake from activating and de-activating as the motor passes through zero speed. If the speed falls below Brake Control:
Brake Apply Speed (D09) and Reference On (D10) = 0 then the brake will be applied.
D10
Reference On
Mode
Open Loop, RFC-A, RFC-S
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
Reference On (D10), which is controlled by the drive sequencer, indicates that the reference from the reference system is active.
D11
Brake Contact Monitoring Select
Mode
Open Loop, RFC-A, RFC-S
Minimum
0
Default
0
Type
8 Bit User Save
Display Format
Standard
Coding
RW, TE, BU
Value
0
None
1
IP 1
2
IP 1 + IP2
When set to Off (0), brake contact monitoring is disabled.
When set to On (1), brake contact 1 monitoring is enabled where Brake Contact Monitoring Input 1 (D12) is monitored to determine the state of the
contactor. It is assumed that if Brake Contact Monitoring Input 1 (D12) = Off (0) the contact is open (brake applied), and if Brake Contact Monitoring
248
Electrical
Getting
User Menu A Commissioning
installation
started
Text
Advanced
Diagnostics Optimization CT MODBUS RTU Technical Data
Parameters
Open-Loop: 20.0
Maximum
RFC-A, RFC-S: 200
Open-Loop: Hz
Units
RFC-A, RFC-S: rpm
Update Rate
4 ms read
Decimal Places
1
Maximum
1
Units
Update Rate
2 ms write
Decimal Places
0
Maximum
2
Units
Update Rate
Background
Decimal Places
0
E300 Design Guide
Issue Number: 1