Trip
Card Error
NV Media Card data structure error
The Card Error trip indicates that an attempt has been made to access a NV Media Card but an error has been detected in
the data structure on the card. Resetting the trip will cause the drive to erase and create the correct folder structure. The
cause of the trip can be identified by the sub-trip.
Sub-trip
182
Recommended actions:
Ensure the NV Media Card is located correctly and is secure
Erase all the data blocks and re-attempt the process
Replace the NV Media Card
NV Media Card full
Card Full
The Card Full trip indicates that an attempt has been made to create a data block on a NV Media Card, but there is not
enough space left on the card.
184
Recommended actions:
Delete a data block or the entire NV Media Card to create sufficient space
Use an alternative NV Media Card
Card No Data
NV Media Card data not found
The Card No Data trip indicates that an attempt has been made to access a non-existent file or data block on a NV Media
Card
183
Recommended actions:
Ensure NV Media Card data block number is correct
NV Media Card trip; option modules installed are different between source drive and destination drive
Card Option
The Card Option trip indicates that parameter data or default difference data is being transferred from a NV Media Card to
the drive, but the option module categories are different between source and destination drives. This trip does not stop the
data transfer, but is a warning that the data for the option modules that are different will be set to the default values and not
the values from the NV Media Card. This trip also applies if a compare is attempted between the data block and the drive.
Recommended actions:
180
Ensure the correct option modules are installed.
Ensure the option modules are in the same option module slot as the parameter set stored.
Press the red reset button to acknowledge that the parameters for one or more of the option modules installed will be at
their default values
This trip can be suppressed by setting Pr mm00 to 9666 and resetting the drive.
Card Product
NV Media Card data blocks are not compatible with the drive derivative
The Card Product trip is initiated either at power-up or when the NV Media Card is accessed, If Drive Derivative (J96) is
different between the source and target drives.
This trip can be reset and data can be transferred in either direction between the drive and NV Media Card.
175
Recommended actions:
Use a different NV Media Card
This trip can be suppressed by setting Pr mm00 to 9666 and resetting the drive
Card Rating
NV Media Card Trip; The voltage and / or current rating of the source and destination drives are different
The Card Rating trip indicates that parameter data is being transferred from a NV Media Card to the drive, but the current
and / or voltage ratings are different between source and destination drives. This trip also applies if a compare (using
Pr mm00 set to 8yyy) is attempted between the data block on a NV Media Card and the drive. The Card Rating trip does
not stop the data transfer but is a warning that rating specific parameters with the RA attribute may not be transferred to the
186
destination drive.
Recommended actions:
Reset the drive to clear the trip
Ensure that the drive rating dependent parameters have transferred correctly
Card Read Only
NV Media Card has the Read Only bit set
The Card Read Only trip indicates that an attempt has been made to modify a read-only NV Media Card or a read-only data
block. A NV Media Card is read-only if the read-only flag has been set (Pr mm00 was set to 9888)
181
Recommended actions:
Clear the read only flag by setting Pr mm00 to 9777 and resetting the drive. This will clear the read-only flag for all data
blocks in the NV Media Card
Card Slot
NV Media Card Trip; Option module application program transfer has failed
The Card Slot trip is initiated if the transfer of an option module application program to or from an application module failed
because the option module does not respond correctly. If this happens this trip is produced with the sub-trip indicating the
option module slot number.
174
Recommended actions:
Ensure the source / destination option module is installed in the correct slot
458
Electrical
Getting
User Menu A Commissioning
installation
started
1
The required folder and file structure is not present
2
The HEADER.DAT file is corrupted
3
Two or more files in the GT8DATA\DRIVE folder have the same file identification number
Advanced
Diagnostics
Optimization CT MODBUS RTU Technical Data
Parameters
Diagnosis
Reason