Behavior Of Drive When Tripped; Trip Reset - Emerson E300 Series Design Manual

Advanced elevator drive / dedicated elevator variable speed ac drive for induction and permanent magnet motors
Hide thumbs Also See for E300 Series:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
9.7

Behavior of drive when tripped

If a drive trip occurs, the following read only parameters are frozen until the trip is reset. This is to assist in diagnosing the cause of the trip. If the
parameter freeze is not required this can be disabled with Action On Trip Detection H45).
Parameter
J31
Speed Error
J32
Speed Loop Output
J22
Total Output Current
J24
Torque Producing Current
J25
Magnetizing Current
J60
Output Frequency
J61
Output Voltage
J59
Output Power
J65
DC bus voltage
F35
T5 T6 Analog Input 1
F36
T7 Analog Input 2
F37
T8 Analog Input 3
9.8

Trip reset

9.8.1
Trip categories and priorities
Trips are grouped into categories which are allocated priorities as detailed below, which can effect how and if a trip reset can be carried out. A trip can
only occur when the drive is not already tripped, or if the drive is already tripped and the new trip occurs which has a higher priority than the current
trip i.e. lower priority number). Unless otherwise stated, a trip cannot be reset until 1.0 s after it has been initiated.
Table 9-5 Trip categories and priorities
Priority
Category, Trips
1
Internal fault, HF01 - HF20
1
Stored HF trip
Non re-settable trip, trip
2
numbers 218 to 247
Volatile memory fault,
3
EEPROM Fail
Internal 24 V power supply,
4
PSU 24 V
NV Media Card trips, trip
5
numbers 174, 175 and 177 to
188
Position feedback power
5
supply, Encoder 1
Trips with extended reset
6
times, OI ac, OI Brake, and OI
dc
Phase loss and DC Bus
6
protection, Phase Loss and
OHt dc bus
6
Standard trips, All other trips
Drive trips can be manually reset using the keypad using communication protocols or using the drives auto reset feature. The manual drive reset is
carried out pressing the RED reset button as shown below in Figure 9-3 Keypad drive reset .
E300 Design Guide
Issue Number: 1
Electrical
Getting
User Menu A Commissioning
installation
started
Description
These are internal faults which cannot be reset, all drive features are rendered inactive.
If a keypad is installed this will display the active HF trip. These trips are not stored in the trip log.
This trip can only be cleared by entering 1299 into Pr mm00 followed by a reset.
These trips cannot be reset.
This trip can only be cleared by entering to 1233 or 1244 into Pr mm00, or if Load Defaults is set to a
non-zero value.
These trips are priority 6 during power up.
This trip can override Encoder 2 to Encoder 6 trips.
These trips can only be reset 10 s after the trip was initiated.
The drive will attempt to stop the motor before tripping phase loss unless disabled.
The drive will attempt to stop the motor before tripping OHt dc bus.
Advanced
Diagnostics
Optimization CT MODBUS RTU Technical Data
Parameters