Trip
OHt dc bus
DC bus over temperature
OHt DC bus trip indicates a DC bus component over temperature based on the software thermal model. The drive includes
a thermal protection system to protect the DC bus components within the drive, this includes the effects of the output
current and DC bus ripple. The estimated temperature is displayed as a percentage of the trip level in parameter
Percentage Of DC Link Thermal Trip Level (J78). If this parameter reaches 100 % then an OHt DC bus trip is initiated. The
drive will attempt to stop the motor before tripping. If the motor does not stop in 10 seconds the drive trips immediately.
Control system
Recommended actions:
Check the AC power supply voltage level
Check the AC power supply voltage balance
Check the DC bus voltage ripple level
27
Reduce motor loading
Check the output current stability and if unstable;
Check the motor map settings within the drive (parameters B06, B02, B07, B03, B04, B05), all modes
Slip Compensation Enable (B10), (Open loop)
Select fixed boost mode, parameter B09 (Open loop)
Disconnect load and complete a rotating autotune, Motor Autotune (B11)
Autotune the rated speed, parameter B07 (Open loop) parameter B25 (RFC-A)
Reduce the speed loop gains, parameters I01, I02, I06 and I07 run and stop (Closed loop operation)
Add a speed feedback filter parameter C09 (Closed loop operation)
Add a current demand filter, parameters I05, I10 run and stop
Check position feedback signals for noise with an oscilloscope (Closed loop operation)
Check encoder mechanical coupling (Closed loop operation)
Reduce duty cycle
OHt Inverter
Inverter over temperature based on thermal model
OHt Inverter trip indicates an IGBT junction over-temperature has been detected based on the software thermal model.
Control system
Recommended actions:
21
Check AC power supply input phases present and balanced
Check DC bus ripple
Check for motor instability
Reduce acceleration / deceleration rates
Reduce the maximum operating switching frequency
Reduce motor load
Reduce duty cycle
OHt Power
Power stage over temperature
OHt Power trip indicates that a power stage over-temperature has been detected. From the sub-trip 'xxyzz', the thermistor
location is identified by 'zz'.
OHt Power is detected at >= 90 % of the maximum threshold on starting a new travel i.e. exiting from Elevator Software
State (J03) = 0 to 1.
If during travel 100 % is reached the drive will trip immediately, where the location of the out of range temperature is
indicated by the sub-trip number as detailed in the table below:
Power system
Recommended actions:
22
Check enclosure / drive fans are still functioning correctly
Check enclosure ventilation paths, door filters
Check correct drive size for the application, load correct
Force heatsink cooling fans to run at maximum speed
Increase enclosure ventilation
Decrease acceleration / deceleration rates
Reduce motor load
Reduce duty cycle
Reduce the drive switching frequency
Use a drive with larger current / power rating
If the temperature is >= 90 % of the maximum then Global Warning (L04) = On (1) indicating that there is a thermal
issue and on the next start the elevator will trip OHt Power.
E300 Design Guide
Issue Number: 1
Electrical
Getting
User Menu A Commissioning
installation
started
Source
xx
00
Source
xx
00
Source
xx
01
Advanced
Parameters
Diagnosis
y
zz
2
00
DC bus thermal model gives trip with sub-trip 0
y
zz
1
00
Inverter thermal model gives (OHt Inverter) trip with sub-trip 0
y
zz
0
zz
Thermistor location in the drive defined by zz
Diagnostics
Optimization CT MODBUS RTU Technical Data