Motor Thermistor Input Select
Mode
Open-Loop, RFC-A, RFC-S
Minimum
0
Default
Type
16 Bit User Save
Display Format
Standard
Coding
RW
When set to 0, a thermistor input is not selected, and T8 Analog Input 3 Mode (F52) is set to Volt or 6.
When set to 1, analog input 3 thermistor input is selected, and T8 Analog Input 3 Mode (F52) is set to Therm No Trip or 9. T8 Analog Input 3
Thermistor Type (F59), T8 Analog Input 3 Thermistor Trip Threshold (F60) and T8 Analog Input 3 Thermistor Reset Threshold (F61) are used to
configure the thermistor input.
When set to 2, the drive encoder thermistor input is selected, and T8 Analog Input 3 Mode (F52) is set to Volt or 6. Encoder Thermistor Type (F69),
Encoder Thermistor Trip Threshold (F70) and Encoder Thermistor Reset Threshold (F71) are used to configure the thermistor input.