Safety
Product
Mechanical
information
information
installation
NOTE
The nominal output cable size assumes the motor maximum current matches that of the drive. Where a motor of reduced rating is used the cable
rating may be chosen to match that of the motor. To ensure that the motor and cable are protected against over-load, the drive must be programmed
with the correct motor rated current.
NOTE
Ensure cables used suit local wiring regulations.
The nominal cable sizes below are only a guide. The mounting and grouping of cables affects their current-carrying capacity, in some cases
smaller cables may be acceptable but in other cases a larger cable is required to avoid excessive temperature or voltage drop. Refer to
local wiring regulations for the correct size of cables.
CAUTION
4.12.1
Cable type
Use 105 °C (221 °F) (UL 60/75 °C (temp rise) PVC-insulated cable with copper conductors having a suitable voltage rating, for the following power
connections:
•
AC supply to external EMC filter (when used)
•
AC supply (or external EMC filter) to drive
•
Drive to motor
•
Drive to braking resistor
Most cables have an insulating jacket between the cores and the armor or shield; these cables have a low capacitance and are recommended.
Table 4-13 Cable ratings (200 V)
Model
Nominal
Maximum
03200050
1.5
03200066
03200080
4
03200106
04200137
6
04200185
8
05200250
10
06200330
16
06200440
25
07200610
35
07200750
07200830
70
E300 Design Guide
Issue Number: 1
Electrical
Getting
User Menu A Commissioning
installation
started
Cable size (IEC)
2
mm
Input
Installation
Nominal
1.5
4
B2
4
6
8
B2
8
10
B2
10
16
25
B2
25
35
70
B2
70
Advanced
Diagnostics Optimization CT MODBUS RTU Technical Data
Parameters
Output
Maximum
Installation
Nominal
4
B2
8
B2
10
B2
25
B2
70
B2
Cable size (UL)
AWG
Input
Maximum
Nominal
14
14
10
12
12
10
10
8
8
8
8
8
8
4
4
3
3
3
2
2
1
1/0
1
1/0
1/0
Output
Maximum
10
8
8
3
1/0
91