Emerson E300 Series Design Manual page 65

Advanced elevator drive / dedicated elevator variable speed ac drive for induction and permanent magnet motors
Hide thumbs Also See for E300 Series:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
Ground connections
4.3.1
Electrochemical corrosion of grounding terminals
Ensure that grounding terminals are protected against
corrosion i.e. as could be caused by condensation.
WARNING
Size 3 and 4
On sizes 3 and 4, the supply and motor ground connections are made
using the M4 studs located either side of the drive near the plug-in power
connector. Refer to Figure 4-6 for additional ground connection.
Figure 4-6 Size 3 and 4 ground connections
3 4
2
1
1
1. Ground connection studs.
2. Additional ground connection.
Size 5
On size 5, the supply and motor ground connections are made using the
M5 studs located near the plug-in power connector. Refer to Figure 4-7
for additional ground connection.
Figure 4-7 Size 5 ground connections
1
1. Ground connection studs.
E300 Design Guide
Issue Number: 1
Electrical
Getting
User Menu A Commissioning
installation
started
2
1
1
Advanced
Diagnostics Optimization CT MODBUS RTU Technical Data
Parameters
Size 6
On a size 6, the supply and motor ground connections are made using
the M6 studs located above the supply and motor terminals. Refer to
Figure 4-8 below.
Figure 4-8 Size 6 ground connections
1. Ground connection studs
65