Load Measurement - Emerson E300 Series Design Manual

Advanced elevator drive / dedicated elevator variable speed ac drive for induction and permanent magnet motors
Hide thumbs Also See for E300 Series:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
Figure 7-19 Fast stop during acceleration
Speed selection
Creep selection
STO, Drive enable
Fast stop enable
Fast stop during
acceleration enable
7.15

Load measurement

During each travel operation, the E300 Advanced Elevator drive can measure the load in the Elevator car and provide an output to the Elevator
controller to indicate the direction of least load. This output can be used during emergency back-up operation for example, where a low voltage back-
up power supply becomes active to indicate the direction in which to travel with the least load.
Table 7-30 Load measurement
Parameter
Load Measurement Direction Output (O01)
Load Measurement Direction Invert (O02)
Load Measurement Value (O03)
Load Measurement Time (O04)
NOTE
The load measurement and direction output for emergency backup operation is only available in RFC-A and RFC-S operating modes.
Figure 7-20 Load measurement
Speed
Motor current
Brake release
E300 Design Guide
Issue Number: 1
Electrical
Getting
User Menu A
installation
started
Run Jerk 3 (
Acceleration
Rate G11
(
)
Run
Jerk 1
(
G13
)
Direction
Final load measurement direction output
Load measurement direction output invert
Load measurement value
Time period for load measurement. Positive value measurement during start, negative value
measurement during travel.
Advanced
Commissioning
Diagnostics Optimization CT MODBUS RTU Technical Data
Parameters
G15
)
Fast stop disabled
- Standard profile, deceleration, creep and stop active
Fast stop enabled
- Fast stop deceleration and fixed 200 ms stop jerk
Detail
Load Measurement Time (
(Negative value = travel ms)
active
O04
)
173