3: Ur Auto (Resistance compensation, stator resistance measured on first start) Resistance compensation is used as in Ur S mode, but the stator
resistance is only measured once when the drive is first enabled. After the test has been completed successfully the mode is changed to Ur mode and
the stator resistance is saved to non volatile memory. If A03 (Parameter Cloning N01) is set to Auto (3) or Boot (4), the stator resistance is written to
an NV Media Card installed in the drive. If the test fails the mode is changed to Ur mode and the stator resistance is not updated.
4: Ur I (Resistance compensation, stator resistance measured at power-up). Resistance compensation is used as in Ur S mode, but the stator
resistance is only measured when the drive is enabled for the first time after each power-up.
RFC-S Action on enable
Parameter value
0
1
2
3
4
A23 (Action On Enable B09) can be used to get the drive to perform a phasing angle test when it is enabled. This test can be used when a non-
absolute encoder is used for motor control feedback in RFC-S mode. The phasing test will measure and update Position Feedback (C13) phase
angle, so that the correct offset is applied to run the motor with the non-absolute position feedback. The test can be selected to occur after power up
and each time the position feedback is re-initialized.
It is not necessary to perform the test on every enable, but this can be selected as shown in Table 6-6 below. If the motor has significant cogging
torque, and is not locked during the test, it is suggested that a long test is selected, otherwise a short test can be used. It should be noted that the
motor inductances (Transient Inductance B33 (Ld) and (No Load B37 (Lq) are checked before the test is carried out, and if the difference is not
sufficient then the drive will trip. Therefore, if the motor inductances have not been measured with an autotune or changed from their default value of
zero the drive will trip when the drive is enabled.
Table 6-6 Action on enable
Action on
enable
Disabled (0)
No phasing test is carried out on enable
Short (1)
A phasing test lasting approximately 0.4 s is carried out on every enable, the output motor contactors must be closed for this test
A phasing test lasting approximately 0.4 s is carried out when the drive is first enabled after power-up, and when the drive is
Short Once (2)
enabled after the position feedback selected is initialized, the output motor contactors must be closed for this test
Long (3)
A phasing test lasting approximately 1.3 s is carried out on every enable, the output motor contactors must be closed for this test
A phasing test lasting approximately 1.3 s is carried out when the drive is first enabled after power-up, and when the drive is
Long Once (4)
enabled after position feedback selected is initialized, the output motor contactors must be closed for this test
E300 Design Guide
Issue Number: 1
Electrical
Getting
User Menu
installation
started
A
Output voltage
characteristic
Motor rated
voltage
B03
B03/2
Voltage
boost
B12
B06 / 2
Text
Disabled
Short
Short Once
Long
Long Once
Advanced
Commissioning
Diagnostics Optimization CT MODBUS RTU Technical Data
Parameters
(Fd)
Output
frequency
B06
Detail
139