Trip
Rectifier over temperature
OHt Rectifier
OHt Rectifier trip indicates that a rectifier over-temperature has been detected. The thermistor location can be identified
from the sub-trip number.
Power system
Recommend actions:
Check enclosure / drive fans are still functioning correctly
102
Check enclosure ventilation paths, door filters
Check the motor and motor cable insulation with an insulation tester
Force the heatsink cooling fans to run at maximum speed
Increase ventilation
Decrease acceleration / deceleration rates
Reduce motor load
Reduce duty cycle
Install an output line reactor or sinusoidal filter
OI ac
Instantaneous output over current detected
The OI ac trip indicates the instantaneous drive output current has exceeded VM_DRIVE_CURRENT_MAX.
Source
Control
system
Power
system
Recommended actions:
Check correct motor set-up
Check correct motor connections
Check for short circuit on the output cabling
3
Check for control sequence of output motor contactors
Check for control sequence of any output shorting contactor
Check integrity of the motor insulation using an insulation tester
Check correct operation of motor mechanical brake
Check feedback device mechanical coupling
Check feedback device wiring
Check feedback signals are free from noise
Has the phase angle autotune been completed (RFC-S)
If seen during autotune reduce the voltage boost (Open loop, RFC-A)
Reduce speed loop gains (I01, I02, I06 and I07 run and stop) – (Closed loop operation)
Reduce current loop gains (I03, I04, I08 and I09 run and stop)
Acceleration/deceleration rate is too short
OI Brake
Braking IGBT over current detected: short circuit protection for the braking IGBT activated
OI Brake trip indicates an over current has been detected in the brake IGBT or the brake IGBT protection has activated.
4
Recommended actions:
Check the brake resistor installation, wiring
Check any external brake resistor protection
Check brake resistor value is > the minimum brake resistance value for the drive model
OI dc
Power module over current detected from IGBT "ON" state voltage monitoring
OI dc trip indicates that the short circuit protection for the drive output stage has been activated.
Recommended actions:
109
Disconnect the motor cable at the drive output and check both motor and motor cable with an insulation tester
Replace the drive
466
Electrical
Getting
User Menu A Commissioning
installation
started
Source
xx
01
xx
00
01
Source
xx
Power
01
system
Advanced
Parameters
Diagnosis
y
Rectifier number
y
zz
Rectifier
number
Instantaneous over-current trip when the measured a.c.
00
current exceeds VM_DRIVE_CURRENT[MAX].
0
y
zz
0
00
Diagnostics
Optimization CT MODBUS RTU Technical Data
zz
Description
zz
Thermistor location defined by zz
Description
Description
Braking IGBT instantaneous over-current trip
E300 Design Guide
Issue Number: 1

Advertisement

Table of Contents
loading

Table of Contents