Diagnostics; Keypad; Status Led; Communications Protocols - Emerson E300 Series Design Manual

Advanced elevator drive / dedicated elevator variable speed ac drive for induction and permanent magnet motors
Hide thumbs Also See for E300 Series:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
9

Diagnostics

The output of the E300 Advanced Elevator drive is disabled under a trip condition preventing further control of the motor. If the motor is running when
the trip occurs a controlled stop is carried out applying the motors brake. The brake control could be carried out by either the E300 Advanced Elevator
drive, Elevator controller or Safety chain preventing uncontrolled operation of the Elevator.
The drive status LED indicator will flash during a drive trip with a 0.5 s duty cycle.
Users must not attempt to repair a drive if it is faulty, nor carry out fault diagnosis other than through the use of the diagnostic features
described in this chapter. If a drive is faulty, it must be returned to an authorized Control Techniques distributor for repair.
WARNING
9.1

Keypad

The keypad display provides information on Trip, Alarm and Status indications for further details refer to the keypad section
9.2

Status LED

The E300 Advanced Elevator drive has a status LED present on the front of the drive, as shown below, and one located on the remote keypad which
provides a visual indication of the drive status. The status LED indicator will flash with a 0.5 s duty cycle if the drive has tripped.
1. Non flashing:
Normal status
2. Flashing:
Trip status
Figure 9-1 Status LED
9.3

Communications protocols

The drive Status, Alarm and Trip codes can be read from the drive using communication protocols. The E300 Advanced Elevator drive has no
communications support as standard, however where communications are required an option module can be installed refer to section 2.8 Options on
page 19
Parameter Drive OK (L05) provides the drive Status and the drive Trips can be read in parameters Trip 0 (L29) the most recent, through to parameter
Trip 9 (L38)
Example
1. Trip code 2 is read from Trip 0 (L29) via serial communications.
2. Checking the trip code in the Serial communications look up table Trip 2 is an Over Volts trip.
Comms
No.
code
3. Look up Over Volts in Table 9-15 Serial communications look up table on page 473
4. Perform checks detailed under Diagnosis.
NOTE
It should be noted that hardware trips (HF01 to HF20) do not have trip numbers, the HF trip will be displayed on the keypad only.
436
Electrical
Getting
User Menu A Commissioning
installation
started
Keypad
Trip
display
2
Over Volts
Advanced
Diagnostics
Optimization CT MODBUS RTU Technical Data
Parameters
Remote keypad
1
2
E300 Design Guide
Issue Number: 1

Advertisement

Table of Contents
loading

Table of Contents