Emerson E300 Series Design Manual page 140

Advanced elevator drive / dedicated elevator variable speed ac drive for induction and permanent magnet motors
Hide thumbs Also See for E300 Series:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
A24 {B16}
Symmetrical current limit
RW
Num
OL
+ VM_MOTOR1_
RFC-A
CURRENT LIMIT %
RFC-S
A24 (Symmetrical Current Limit B16)
The symmetrical current limit controls the current when the motor is being accelerated away from standstill during constant speed with changing load
levels and during deceleration towards standstill. The maximum possible symmetrical current limit (+ VM_MOTOR1_CURRENT_LIMIT %) varies
between drive sizes with default parameters loaded.
Setting the Symmetrical Current Limit (B16) to a low value or zero can result in uncontrolled movement on brake release. Ensure the
Symmetrical Current Limit (B16)is set to a suitable value taking into account both the motor rated current and overload requirement in the
worst case load condition to avoid uncontrolled movement and the risk of damage to the system.
WARNING
A25 {B13}
Maximum Switching Frequency
RW
Txt
OL
2 kHz (0), 3 kHz (1),
4 kHz (2), 6 kHz (3),
RFC-A
8 kHz (4), 12 kHz (5),
16 kHz (6)
RFC-S
A25 (Maximum Switching Frequency B13)
Value
Text (kHz)
0
1
2
3
4
5
6
This parameter defines the PWM switching frequency. The drive may automatically reduce the switching frequency (without changing this parameter)
if the power stage becomes too hot. A thermal model of the IGBT junction temperature is used based on the heatsink temperature and an
instantaneous temperature drop using the drive output current and switching frequency. The full range of switching frequencies is not available on all
ratings.
The estimated IGBT junction temperature is displayed in
based on the current settings. Reducing the switching frequency, reduces the drive losses and the estimated IGBT junction temperature. If the load
condition persists the estimated IGBT junction temperature may continue to rise again above 145 °C and if the drive cannot reduce the switching
frequency any further the drive will initiate an 'OHt Inverter' trip.
Every second the drive will attempt to restore the switching frequency to the level set in A25 (Maximum Switching Frequency B13).
The control over the drive switching frequency based upon the estimated IGBT junction temperature can be adjusted using the following parameters
Maximum Switching Frequency (B13), Minimum Switching Frequency (B14) and Switching Frequency Step Size (B15).
A26 {B11}
Motor Autotune
RW
Txt
None (0), Static (1),
OL
Rotating (2)
RFC-A
None (0), Static (1),
Rotating (2), Inertia (3)
RFC-S
A26 (Motor Autotune B11)
140
Electrical
Getting
User Menu
installation
started
US
165.0 %
175.0 %
RA
US
8 kHz (4)
2
3
4
6
8
12
16
J77.
NC
None (0)
Advanced
Commissioning
A
Parameters
If this temperature exceeds 145 °C, the switching frequency is reduced if possible,
US
Diagnostics Optimization CT MODBUS RTU Technical Data
E300 Design Guide