Safety
Product
Mechanical
information
information
installation
Trip
Power Comms
Communication has been lost / errors detected between power, control and rectifier modules
A Power Comms trip indicates a communications problem within the power system of the drive. The reason for the trip can
be identified by the sub-trip number.
Type of drive
Single power
90
module system
Recommended actions:
Hardware fault - contact the supplier of the drive.
Power Down Save
Power down save error
The Power Down Save trip indicates that an error has been detected in the power down save parameters saved in non-
volatile memory.
37
Recommended actions:
Perform a 1001 save in Pr mm00 to ensure that the trip doesn't occur the next time the drive is powered up.
PSU
Internal power supply fault
The PSU trip indicates that one or more internal power supply rails are outside their limits or overloaded.
Source
Control
system
Power
5
system
Recommended actions:
Remove keypad from the drive and perform a reset
Remove any option modules and perform a reset
Remove encoder connection and perform a reset
Hardware fault within the drive – return the drive to the supplier
PSU 24V
24V internal power supply overload
The total user load of the drive and option modules has exceeded the internal + 24 V power supply limit. The user load
consists of the drive digital outputs and main encoder supply.
Recommended actions:
Reduce the load and reset the drive
9
Remove control connections from the drive and perform a reset
Remove any option modules and perform a reset
Remove encoder connection and perform a reset
Provide an external + 24 V power supply on Control Terminal 2 of the drive
Permanent trip, hardware fault within the drive – return the drive to the supplier
Resistance
Measured resistance has exceeded the parameter range
The Resistance trip indicates that the measured motor stator resistance during an autotune test has exceeded the
maximum possible value allowable for the drive in Stator Resistance (B34)
Recommended actions:
Check the motor phase to phase resistance at the drive terminals
Check the motor phase to phase resistance at the motor terminals
33
Ensure the drives output stator resistance measurement for the motor falls within the range of the drive model
Check the motor power cable connections
Check the integrity of the motor stator winding using a insulation tester
Select a suitable drive model for the motor
Replace the motor
Slot App Menu
Application menu Customization conflict error
The Slot App Menu trip indicates that more than one option slot has requested to customize the application menus S, T and
U. The sub-trip number indicates which option slot has been allowed to customize the menus.
216
Recommended actions:
Ensure that only one of the Application modules is configured to customize the application menus S, T and U.
E300 Design Guide
Issue Number: 1
Electrical
Getting
User Menu A Commissioning
installation
started
xx
01
xx
00
Rectifier
01
number
Advanced
Diagnostics
Parameters
Diagnosis
y
00: Excessive communications errors detected by the
Rectifier number
rectifier module
y
zz
0
00
Internal power supply overload.
Optimization CT MODBUS RTU Technical Data
zz
Description