Emerson E300 Series Design Manual page 180

Advanced elevator drive / dedicated elevator variable speed ac drive for induction and permanent magnet motors
Hide thumbs Also See for E300 Series:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
Figure 7-24 Floor sensor correction logic diagram
Creep to floor and direct to floor mode
Digital
Input 5
T28
Digital
Input Y
Txx
Creep to floor mode only
Floor sensor correction utilizes a feature of digital input 5, which bypasses the normal input logic resulting in a fast response to a change in the input
signal, such that when the sensor is activated the position is sampled in <1 µs. When digital input 5 is used for floor sensor correction, it is
recommended that the input is not used for any other purpose and Digital Input 5 Destination (F22) should be set to a value of 'A00'. It is possible to
specify whether the positive or negative edge of the floor sensor correction signal is detected using Floor Sensor Correction Edge Detection (H25).
Figure 7-25 Floor sensor correction modes
Profile
Floor sensor correction is enabled via detection of the floor sensor correction signal connected to digital input 5. Travel within
Direct to floor
Floor Sensor Correction Target Distance (G31) is position controlled, modifying the profile as required.
Floor sensor correction is enabled via detection of the floor sensor correction signal connected to digital input 5. Travel within
Floor Sensor Correction Target Distance (G31) is position controlled, modifying the profile (deceleration and jerk rates) as
required.
Creep to floor
Floor sensor correction is enabled via de-selection of the creep speed reference. Travel within Floor Sensor Correction Target
Distance (G31) is position controlled, modifying the profile (deceleration and jerk rates) as required.
7.21.1
Floor sensor correction, direct to floor, on detection of signal via digital input 5
When the floor sensor correction signal is detected, travel within Floor Sensor Correction Target Distance (G31) is position controlled, modifying the
profile (deceleration and jerk rates) as required.
Once the floor sensor correction signal becomes active, the remaining controlled distance to the floor level is displayed in Remaining Floor Sensor
Correction Distance (J47). The speed at the point floor sensor became active is displayed in Speed At Floor Sensor Correction Active (J46).
Figure 7-26 Floor sensor correction, direct to floor, on detection of signal via digital input 5
Floor sensor correction enable
Floor sensor correction signal
NOTE
It should be noted that the floor sensor correction signal should be activated instantaneously at a position which is Floor Sensor Correction Target
Distance (G31) away from the floor sensor in mm. If the stop distance is too low or the floor sensor signal was given at too high a speed (see Speed
At Floor Sensor Correction Active (J46)) the elevator may not be able to stop smoothly and therefore a hard stop will be implemented.
180
Electrical
Getting
User Menu A
installation
started
Digital
Digital
Input 5
Input 5
State
Destination
Invert
F16
F07
Digital
Input Y
Digital
State
Input Y
Invert
Creep
Speed
Select
Speed signals
Floor Sensor Correction Enable (
Control Terminal 28
Target distance
Floor Sensor Correction Target Distance (
Remaining distance
Remaining Floor Sensor Correction Distance (
Floor sensor
Advanced
Commissioning
Parameters
Floor Sensor
Floor Sensor
Correction
Correction
Source
Edge Detection
Select
Digital
H25
Input 5
F22=A00
0
Digital
Input Y
1
Destination
Loss Of
Creep
G52
Speed
Floor Sensor Correction Mode
Run jerk 3 (
G15
)
Deceleration rate(
G12
Target
Deceleration and jerk controlled
correction
by the profile generator to
distance
stop within the target distance
H23
)
G31
)
J47
)
Diagnostics Optimization CT MODBUS RTU Technical Data
Floor Sensor
Correction
Enable
H24
H23
0
Floor Sensor
1
Correction
Trigger
)
E300 Design Guide
Issue Number: 1

Advertisement

Table of Contents
loading

Table of Contents